11 of 17
DESCRIPTION:
DATE:
DRAWING NO:
INSTALLATION NOTES
SHEET:
REVISION:
E
164201037−1
113004
Customer Information
A−12
EATON
Powerware
®
9315 UPS (200–300 kVA) Installation Manual
S
164201037 Rev G
www.powerware.com
8.
Output overcurrent protection and output disconnect switch are to be provided by the user.
Table L lists the maximum rating for output circuit breakers satisfying the criteria for both.
Table L. Maximum Output Circuit Breaker Ratings
Powerware System
Output Voltage Rating
208V
400V
480V
600V
Powerware 9315 200
N/A
400
N/A
N/A
Powerware 9315 225
800
N/A
350
N/A
Powerware 9315 250
N/A
450
N/A
N/A
Powerware 9315 300
1000
N/A
450
400
9.
Table M lists the maximum rating for remote battery disconnect circuit breakers.
Table M. Maximum Remote Battery Disconnect Circuit Breaker Ratings
Powerware 9315 System
Circuit Breaker Rating
DC Voltage
0.8 load pF
0.9 load pF
Model 200
600
700
420
Model 225
600
700
480
Model 250
800
800
420
Model 300
800
1000
480