2 Installation
2.3 COM Port
14
CANopen for DA1, DC1, DE11
09/16 MN040019EN
www.eaton.com
2.3.2 Baud rate
The baud rate must be set to the same value for all the communication
modules on the CANopen bus. A value between 125 and 1000 kBit/s can be
selected for the variable frequency drives‘ baud rate.
The maximum cable length will depend on the baud rate you use.
Table 5:
Maximum cable length and baud rate
Baud rate
Maximum cable length
125 kbit/s
500 m
250 kBit/s
M 250
500 kBit/s (= default setting)
100 m
800 kBit/s
50 m
1000 kBit/s
30 m
Summary of Contents for PowerXL DA1