34
22
DA1
Enc-05
Channel B fault
35
23
DA1
Enc-06
Error on channels A and B
40
28
DA1, DC1…E1
AtF-01
Motor identification failed
41
29
DA1, DC1…E1
AtF-02
Motor identification failed:
The measured stator resistance is too large.
42
2B
DA1, DC1…E1
AtF-03
Motor identification failed:
The measured motor inductance is too low.
43
2B
DA1, DC1…E1
AtF-04
Motor identification failed:
The measured motor inductance is too high.
44
2C
DA1, DC1…E1
AtF-05
Motor identification failed:
The measured motor parameters do not match.
49
31
DA1, DC1…E1
Out-Ph
A phase in the motor cable is not connected or has a discontinuity.
50
32
DA1, DC1…E1
Sc-FO1
No valid Modbus frame was received within the time specified.
51
33
DA1, DC1…E1
Sc-FO2
No valid CANopen frame was received within the specified time.
52
34
DA1
Sc-FO3
Communications between the device and the plugged-in field bus option have dropped
out.
53
35
DA1
Sc-F04
Communications between the device and the plugged-in I/O expansion have dropped out.
60
3C
DA1
OF-01
No internal connection to an optional card
61
3D
DA1
OF-02
Optional module in abnormal state
70
46
DA1
PLC-01
Non-supported function block from function block editor
71
47
DA1
PLC-02
Program from function block editor is too big
72
48
DA1
PLC-03
Division by zero
73
49
DA1
PLC-04
Lower limit is higher than upper limit
74
4A
DA1
PLC-05
Overflow table Function block editor
Error no.
Device series
Message
(display on DA1, DC1)
Possible cause
dec
hex
Summary of Contents for PowerXL DA1