4 CANopen communication settings
4.7 Parameters
54
CANopen for DA1, DC1, DE11
09/16 MN040019EN
www.eaton.com
209B
P-55
RO1 Switch-On Delay
rw
RUN
300
≙
3.00 s
0.0 s - 250.0 s
U16
209C
P-56
Reserved Parameter
rw
RUN
300
≙
3.00 s
0.0 s - 250.0 s
U16
209D
P-57
Reserved Parameter
rw
RUN
300
≙
3.00 s
0.0 s - 250.0 s
U16
209E
P-58
Reserved Parameter
rw
RUN
300
≙
3.00 s
0.0 s - 250.0 s
U16
209F
P-59
Reserved Parameter
rw
RUN
300
≙
3.00 s
0.0 s - 250.0 s
U16
20A0
P-60
Motor Control Mode
rw
RUN
1
≙
1
0 - 4
U16
20A1
P-61
Motor Identification
rw
RUN
300
≙
3.00 s
0.0 s - 250.0 s
U16
20A2
P-62
MSC Gain
rw
RUN
10
≙
1.0 %
0.0 % - 200.0 %
U16
20A3
P-63
I-CurrentLimit
rw
RUN
10
≙
1.0 %
0.1 % - 175 %
U16
20A4
P-64
Motor Stator Resistance R1
rw
RUN
100
≙
1.00
Ω
0.00
Ω
- 655.35
Ω
U16
20A5
P-65
Motor Stator Inductance d-
Axis
rw
RUN
100
≙
10.0 mH
0.0 mH - 6553.5 mH
U16
20A6
P-66
Motor Stator Inductance q-
Axis
rw
RUN
100
≙
10.0 mH
0.0 mH - 6553.5 mH
U16
20A7
P-67
f-DCBrake@Stop
rw
RUN
3000
≙
50.0 Hz
0.0 Hz - P-01
U16
20A8
P-68
DC-Brake Current
rw
RUN
10
≙
1.0 %
0.0 % - 100.0 %
U16
2013
P00-01
Analog Input1
ro
RUN
10
≙
1.0 %
0 - 1000
U16
2014
P00-02
Analog Input2
ro
RUN
10
≙
1.0 %
0 - 1000
U16
2012
P00-04
DI1 Status
ro
RUN
U16
2049
P00-05
PID1 Output
ro
RUN
10
≙
1.0 %
0 - 1000
U16
2048
P00-07
Motor voltage
ro
RUN
100
≙
100 VAC
RMS
0 - 500
U16
2011
P00-08
DC Link Voltage
ro
RUN
230
≙
230 V
0 - 1000
U16
203E
P00-10
t-Run hours
ro
RUN
100
≙
100 h
U16
203F
P00-10
t-Run seconds
ro
RUN
100
≙
100 s
U16
27D0
P00-11
t-Run since Trip hours
ro
RUN
100
≙
100 h
U16
27D1
P00-11
t-Run since Trip seconds
ro
RUN
100
≙
100 s
U16
27D2
P00-12
t-Run since Trip hours
ro
RUN
100
≙
100 h
U16
27D3
P00-12
t-Run since Trip seconds
ro
RUN
100
≙
100 s
U16
27D4
P00-13
Last Fault1 PDP
ro
RUN
U16
27D4
P00-13
Last Fault2 PDP
ro
RUN
U16
27D5
P00-13
Last Fault3 PDP
ro
RUN
U16
27D5
P00-13
Last Fault4 PDP
ro
RUN
U16
27D6
P00-13
Last Fault1 PDP hours
ro
RUN
100
≙
100 h
U16
27D7
P00-13
Last Fault1 PDP seconds
ro
RUN
100
≙
100 s
U16
27D8
P00-13
Last Fault2 PDP hours
ro
RUN
100
≙
100 h
U16
27D9
P00-13
Last Fault2 PDP seconds
ro
RUN
100
≙
100 s
U16
27DA
P00-13
Last Fault3 PDP hours
ro
RUN
100
≙
100 h
U16
CANopen
Index [hex]
Param
eter
Designation
Access
Scale
Value range
Data
format
rw/
ro
RUN/
STOP
Summary of Contents for PowerXL DA1