5 Parameters
5.1 “Monitor” parameter group
DB1 Variable Frequency Drives
09/17 MN040034EN
www.eaton.com
29
5 Parameters
The following tables use a number of acronyms. These acronyms are defined
below:
5.1 “Monitor” parameter group
Table 20: “Monitor” parameter group
Abbreviation
Meaning
min. value
Minimum value
max. value
Maximum value
DS
Default setting (the parameter's value when using the device's
factory settings)
→
None of the parameters in parameter group 0 can be modified
by the user, i.e., they are read-only parameters.
Parameter
Name
min. value
max. value
Description
P00-01
AI1
0
100%
Analog input 1
Level of the signal applied to analog input 1 after
scaling and offsets have been applied.
P00-02
Analog input 2
0
100%
Analog input 2
Level of the signal applied to analog input 2 after
scaling and offsets have been applied.
P00-03
Frequency setpoint
-P-01
P-01
Frequency Reference in Hz.
Will be calculated into rpm when motor data are
available.
Value of the drive internal digital reference.
P00-04
DI1 Status
0
1
Digital input status
Status of the digital inputs starting on the left hand
side with digital input 1 etc.
DI2 Status
0
1
DI3 Status
0
1
DI4 Status
0
1
DI5 Status
0
1
P00-05
PID1 Output
0
100%
PI(D) controller 1 Output
P00-06
DC-Link Voltage Ripple
0
1000V
DC-Link Voltage Ripple
P00-07
Motor voltage
0V
600VAC
Instantaneous output voltage
P00-08
DC link voltage
0V
1000VDC
Instantaneous DC Link Voltage
P00-09
Actual Switching Frequency
-20°C
100°C
Instantaneous Heatsink Temperature
P00-10
t-Run
0 h
99999 h
Total operating time of the drive since the date of
manufacture
P00-11
t-Run since Trip
0 h
65000 h
Total operating time of the drive since the last trip
occurred