User Manual 

MN040024EN

Effective November 2016

DX-NET-ETHERNET2-2 fi eld bus connection
EtherNet/IP for variable frequency drive DE1/DC1

EATON

 www.eaton.com

Before commencing the installation

• Disconnect the power supply of the device.

• Ensure that devices cannot be accidentally restarted.

• Verify isolation from the supply.

• Earth and short circuit the device.

• Cover or enclose any adjacent live components.

• Follow the engineering instructions (AWA/IL) for the 

device concerned.

• Only suitably qualified personnel in accordance with 

EN 50110-1/-2 (VDE 0105 Part 100) may work on this 
device/system.

• Before installation and before touching the device ensure 

that you are free of electrostatic charge.

• The functional earth (FE, PES) must be connected to the 

protective earth (PE) or the potential equalisation. The 
system installer is responsible for implementing this 
connection.

• Connecting cables and signal lines should be installed so 

that inductive or capacitive interference does not impair 
the automation functions.

• Install automation devices and related operating elements 

in such a way that they are well protected against 
unintentional operation.

• Suitable safety hardware and software measures should 

be implemented for the I/O interface so that an open 
circuit on the signal side does not result in undefined 
states in the automation devices.

• Ensure a reliable electrical isolation of the extra-low 

voltage of the 24 V supply. Only use power supply units 
complying with IEC 60364-4-41 (VDE 0100 Part 410) or 
HD384.4.41 S2.

• Deviations of the mains voltage from the rated value must 

not exceed the tolerance limits given in the specifications, 
otherwise this may cause malfunction and dangerous 
operation.

• Emergency stop devices complying with IEC/EN 60204-1 

must be effective in all operating modes of the automation 
devices. Unlatching the emergency-stop devices must not 
cause a restart.

• Devices that are designed for mounting in housings or 

control cabinets must only be operated and controlled 
after they have been installed and with the housing 
closed. Desktop or portable units must only be operated 
and controlled in enclosed housings.

• Measures should be taken to ensure the proper restart of 

programs interrupted after a voltage dip or failure. This 
should not cause dangerous operating states even for a 
short time. If necessary, emergency-stop devices should 
be implemented.

• Wherever faults in the automation system may cause 

injury or material damage, external measures must be 
implemented to ensure a safe operating state in the event 
of a fault or malfunction (for example, by means of 
separate limit switches, mechanical interlocks etc.).

• Depending on their degree of protection, frequency 

inverters may contain live bright metal parts, moving or 
rotating components or hot surfaces during and 
immediately after operation.

• Removal of the required covers, improper installation or 

incorrect operation of motor or frequency inverter may 
cause the failure of the device and may lead to serious 
injury or damage.

• The applicable national accident prevention and safety 

regulations apply to all work carried on live frequency 
inverters.

• The electrical installation must be carried out in 

accordance with the relevant regulations (e. g. with 
regard to cable cross sections, fuses, PE).

• Transport, installation, commissioning and maintenance 

work must be carried out only by qualified personnel 
(IEC 60364, HD 384 and national occupational safety 
regulations).

• Installations containing frequency inverters must be 

provided with additional monitoring and protective 
devices in accordance with the applicable safety 
regulations. Modifications to the frequency inverters 
using the operating software are permitted.

• All covers and doors must be kept closed during 

operation.

• To reduce the hazards for people or equipment, the user 

must include in the machine design measures that restrict 
the consequences of a malfunction or failure of the drive 
(increased motor speed or sudden standstill of motor). 
These measures include:

– Other independent devices for monitoring safety-

related variables (speed, travel, end positions etc.).

– Electrical or non-electrical system-wide measures 

(electrical or mechanical interlocks).

– Never touch live parts or cable connections of the 

frequency inverter after it has been disconnected from 
the power supply. Due to the charge in the capacitors, 
these parts may still be live after disconnection. Fit 
appropriate warning signs.

Danger!
Dangerous electrical voltage!

Summary of Contents for PowerXL DX-NET-ETHERNET2-2

Page 1: ...User Manual MN040024EN Effective November 2016 New information PowerXL DX NET ETHERNET2 2 fieldbus connection EtherNet IP for variable frequency drive DE1 DC1...

Page 2: ......

Page 3: ...OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON THE C...

Page 4: ...istributors or Eaton s sales offices Website address www eaton com drives EatonCare customer support center Call the EatonCare Support Center if you need assistance with placing an order stock availab...

Page 5: ...sings Measures should be taken to ensure the proper restart of programs interrupted after a voltage dip or failure This should not cause dangerous operating states even for a short time If necessary e...

Page 6: ...troduction 6 Installing the fieldbus connection 6 Install fieldbus 6 Commissioning 7 DE1 DC1 variable frequency drives 7 EDS file 7 Engineering the module 7 Addressing 8 Web server 11 Operation 13 App...

Page 7: ...et system Further manuals for this device Further information can be found in the following manuals On the topic Variable frequency drive DC1 MN040022_EN DC1 Enhanced MN040023EN DE1 MN040011EN Writing...

Page 8: ...1 EATON www eaton com Device series Checking the delivery The packaging must contain the following part An EIP interface card DX NET EtherNet2 2 Key to part numbers The catalog number selection and th...

Page 9: ...interface A B The electrical connection between the master and the slaves is established with RJ 45 cables If multiple slaves are being used they are connected in parallel by using RJ 45 cables and DX...

Page 10: ...general rated operational data as well as all EtherNet IP specific technical data is adhered to However external factors can influence the components s lifespan and function We therefore recommend th...

Page 11: ...ction timeout Steady Red Duplicate IP Flashing Green and Red Self test MS Module Status The module status LED MS is used to indicate the EtherNet IP module s status Table 2 Module status indicator Sta...

Page 12: ...ble as standard ready for use cables They can also be prepared individually This will require the connections shown below pinout Install fieldbus When installing the connection make sure that the cont...

Page 13: ...to configure parameters please refer to user manual EDS file The properties of an EtherNet IP card are described in the corresponding EDS file This file is required in order to be able to integrate a...

Page 14: ...1 holding register 0 0x10 Set_Attribute_Single 0x44 Modbus Object 0x4E Read_Holding_Registers Multiple parameter Read Write Instance 1 holding register 0 0x50 Write_Holding_Registers 0x04 Assembly Ob...

Page 15: ...quency drive x Connect the device to the computer and to the network x Switch on the VFD x Open the web browser x Type in the IP address or hostname on the module in the web browser to open the web se...

Page 16: ...l be displayed Table 8 Status State Indication Data Submitted Data has been submitted to DX NET ETHERNET2 2 awaiting reply Data Read Write Error An error occurred data was not stored Resource Busy Ano...

Page 17: ...ber Module production serial number ODVA EtherNet IP Vender ID Module vendor ID on EIP Product Code EIP registered product code Protocol Serial Number EIP protocol serial number for addressing MAC Add...

Page 18: ...efines the subnet mask of the network Gateway Address defines the address of the connected gateway Name Server defines the Server 1 address location Name Server 2 defines the Server 2 address location...

Page 19: ...C 06 RPI Min 50 ms Timeout multiplier Recommend x32 Trigger Cyclic Transport type Exclusive owner OAT Size 8 Connection Type Point to Point Length Fixed Transfer Format 32 bit Run Idle TAO Size 8 Conn...

Page 20: ...ric integer input tags and 4 generic integer output tags for the DC1 DE1 These tags do contain the name provided for this device The data layouts for the 4 input and output words are described below E...

Page 21: ...01 maximum frequency This value will be scaled with a factor of 0 1 in the application 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 MSB LSB Process data input 3 PDI3 not used The value is not used Process da...

Page 22: ...frequency drive DE1 DC1 EATON www eaton com Output process data field DE1 DC1 Status and Fault Word Information regarding the device status and fault messages is specified in the status and fault wor...

Page 23: ...Byte Instance 2 Modbus Register Holding Register 2 PDI2 2 Byte Instance 3 Modbus Register Holding Register 3 PDI3 2 Byte Instance 4 Modbus Register Holding Register 4 PDI4 2 Byte Instance 5 Modbus Reg...

Page 24: ...x18 10 0 P00 03 Reference input speed R S16 22 0x18 9 0 P00 08 DC link voltage R U16 23 0x18 8 0 P00 09 Temperature in power section R S16 24 0x18 7 0 P00 10 DE1 operating time R 25 0x18 6 0 DE1 opera...

Page 25: ...7 0x19 0 26 DC braking time R W U16 154 0x18 16 0x19 0 27 DC braking voltage R W U16 155 0x18 15 0x19 0 28 DC braking frequency R W U16 156 0x18 14 0x19 0 29 Switching frequency R W U16 157 0x18 13 0x...

Page 26: ...03 Reference input speed R S16 22 0x4E 9 P00 08 DC link voltage R U16 23 0x4E 8 P00 09 Temperature in power section R S16 24 0x4E 7 P00 10 DE1 operating time R 25 0x4E 6 DE1 operating time R 26 0x4E...

Page 27: ...0x4E 17 0x50 1 26 DC braking time R W U16 154 0x4E 16 0x50 1 27 DC braking voltage R W U16 155 0x4E 15 0x50 1 28 DC braking frequency R W U16 156 0x4E 14 0x50 1 29 Switching frequency R W U16 157 0x4...

Page 28: ...eference input speed R S16 22 0x0E P00 08 DC link voltage R U16 23 0x0E P00 09 Temperature in power section R S16 24 0x0E P00 10 DE1 operating time R 25 0x0E DE1 operating time R 26 0x0E P00 12 DE1 op...

Page 29: ...0x0E 0x10 26 DC braking time R W U16 154 0x0E 0x10 27 DC braking voltage R W U16 155 0x0E 0x10 28 DC braking frequency R W U16 156 0x0E 0x10 29 Switching frequency R W U16 157 0x0E 0x10 30 Start mode...

Page 30: ...emperature R S16 24 0x18 7 0 Variable frequency drive operating time R 25 0x18 6 0 Variable frequency drive operating time R 26 0x18 5 0 The variable frequency drive operating time since the last faul...

Page 31: ...t braking R W U16 160 0x18 22 0x19 22 P 33 Motor pick up control function to catch spinning motors in sizes FS2 and FS3 DC braking braking time at start in size FS1 R W U16 161 0x18 21 0x19 21 P 34 Br...

Page 32: ...re R S16 24 0x4E 7 Variable frequency drive operating time R 25 0x4E 6 Variable frequency drive operating time R 26 0x4E 5 The variable frequency drive operating time since the last fault R 27 0x4E 4...

Page 33: ...current braking R W U16 160 0x4E 22 0x50 1 P 33 Motor pick up control function to catch spinning motors in sizes FS2 and FS3 DC braking braking time at start in size FS1 R W U16 161 0x4E 21 0x50 1 P...

Page 34: ...24 0x0E Variable frequency drive operating time R 25 0x0E Variable frequency drive operating time R 26 0x0E The variable frequency drive operating time since the last fault R 27 0x0E The variable freq...

Page 35: ...ent braking R W U16 160 0x0E 0x10 P 33 Motor pick up control function to catch spinning motors in sizes FS2 and FS3 DC braking braking time at start in size FS1 R W U16 161 0x0E 0x10 P 34 Brake choppe...

Page 36: ...cted to an Ethernet network select the Local Area Connection Unless the computer is connected to a network this Local Area Connection will not be present 3 The Local Area Connection Status window will...

Page 37: ...1 254 default CompactLogix 192 168 1 2 Computer 192 168 1 51 Subnet mask 255 255 255 0 Connect your computer PLC and the PowerXL DC1 DE1 drive to an Ethernet switch To configure the IP address of the...

Page 38: ...with RSLogix5000 version 20 or later These files can be installed into the RSLogix5000 software via the following 1 Download the EDS files for Eaton EtherNet IP products from the following link www ea...

Page 39: ...herNet IP for variable frequency drive DE1 DC1 EATON www eaton com Creating an EtherNet IP network in RSLogix5000 On the Controller Organizer on the left portion of the project screen in RSLogix5000 n...

Page 40: ...of the window Then select Eaton Electrical to check the box to its left and only Eaton products will be displayed below as follows Select the DX NET ETHERNET2 2 from the list then select Create This...

Page 41: ...AOI creates all I O tags in the proper data type such as BOOL Bytes and Words It also handles all the scaling and provides data in engineering units The AOI can be used as many times in your program a...

Page 42: ...to be used They have been created in the Controller Tags area as follows Note there are 4 generic integer input tags and 4 generic integer output tags for the DC1 DE1 These tags do contain the name p...

Page 43: ...cfg and aes files must match x Set the IP address of the DX NET ETHERNET2 2 to its default settings either via an Identity Class Type 1 reset or via the Webserver The values should be as follows Confi...

Page 44: ...steps defined within Performing Firmware upgrade Primary bootloader indicator states PBL power up the following LED test sequence is performed in parallel Network Status Indicator 1 Hz double flash Am...

Page 45: ...39 User Manual MN040024EN Effective November 2016 DX NET ETHERNET2 2 field bus connection EtherNet IP for variable frequency drive DE1 DC1 EATON www eaton com...

Page 46: ...40 User Manual MN040024EN Effective November 2016 DX NET ETHERNET2 2 field bus connection EtherNet IP for variable frequency drive DE1 DC1 EATON www eaton com...

Page 47: ...41 User Manual MN040024EN Effective November 2016 DX NET ETHERNET2 2 field bus connection EtherNet IP for variable frequency drive DE1 DC1 EATON www eaton com...

Page 48: ...ing a world that demands more With over 100 years experience in electrical power management we have the expertise to see beyond today From ground breaking products to turnkey design and engineering se...

Reviews: