background image

4 Commissioning

4.3 Cyclic data

DX-NET-SWD

06/13 MN04012009Z-EN

www.eaton.com

33

4.3.5 Profile 2 (2 x 16 bit): Outputs (control)

Output bytes 0 and 4 are mapped as follows on SmartWire-DT.

Table 9:

Profile 11: Output bytes 0 and 4

Word

BIT

designation

Meaning

0

0

OnOff

On/Off
0: Normal stop (with configured ramp time)
1: Operation

1

Off2

Run-down (Coast Stop: Off 2)
0: Coast stop (switch off output voltage)
1: no free run-down

2

Off3

Quick Stop: Off3
0: Quick stop (shortest ramp)
1: no quick stop

3

EN_Op

Operation released
0: Stop
1: Operation 

4

EN_Ramp

Release ramp (Enable Ramp Generator)
0: Reset ramp (setpoint value = 0)
1: Release ramp

5

Unfreeze

Unfreeze ramp
0: Freeze ramp (the ramp generator's current output value will be 
frozen)
1: Do not freeze ramp

6

EN_Set

Activate setpoint value:
EN_Set enables the setpoint value and starts or stops the motor 
with the ramp function.
0: Do not activate setpoint value
1: activate setpoint value

7

FaultAck

Fault Acknowledge
0: Do not acknowledge current fault
1: Acknowledge current fault (rising edge: 0 

 1)

8

Jog 1

Jog with setpoint value 1

9

Jog 2

Jog with setpoint value 2

10

Ctl_PLC

PLC assumes control (Control by PLC)
0: no control via PLC
1: Control via PLC

11

I1

programmable input 1

12

I2

programmable input 2

13

I3

programmable input 3

14

I4

programmable input 4

15

ExtFault

External Fault
If the bit is set, the DC1 variable frequency drive will stop with a 
selected PNU 840 function. The behavior is the same as if there 
were a change from 1 

 0 in the Enable signal, with the exception 

that the variable frequency drive soft starter will switch to the Error 
status (input bytes n + 4: bit 3). The external fault can be reset just 
like any other fault (with Fault acknowledge (bit 7) or by switching 
the supply voltage off and on).
0: no external fault
1: external fault

1

0 - 15

Setpoint

setpoint input in percent from -100 % to + 100 %;
100 % 

 

4000

hex

Summary of Contents for PowerXL DX-NET-SWD

Page 1: ...Manual PowerXL DX NET SWD Interface card SmartWire DT for Variable Frequency Drives DC1 SmartWire DT The easy way to connect 06 13 MN04012009Z EN ...

Page 2: ...s document other than those in German language are translations of the original German manual 1st published 2013 edition date 06 13 2013 by Eaton Industries GmbH 53105 Bonn Production René Wiegand Translation globaldocs GmbH All rights reserved including those of the translation No part of this manual may be reproduced in any form printed photocopy microfilm or any other process or processed dupli...

Page 3: ...e dip or failure This should not cause dangerous operating states even for a short time If necessary emergency stop devices should be implemented Wherever faults in the automation system may cause injury or material damage external measures must be implemented to ensure a safe operating state in the event of a fault or malfunction for example by means of separate limit switches mechanical interloc...

Page 4: ...II ...

Page 5: ...eries 7 1 1 Checking the Delivery 7 1 1 1 Key to part numbers 8 1 1 2 General rated operational data 8 1 2 Designation at DX NET SWD3 9 1 3 Proper use 10 1 4 Maintenance and inspection 11 1 5 Storage 11 1 6 Service and warranty 11 1 7 Disposal 11 2 Engineering 13 2 1 SmartWire DT 13 2 2 LED SmartWire DT diagnostics LED 14 2 3 1 0 A switch 14 2 4 Interoperability 15 2 4 1 Gateways 15 2 4 2 Fieldbus...

Page 6: ... State diagrams 24 4 3 Cyclic data 28 4 3 1 Introduction 28 4 3 2 Profile 1 8 bit Inputs status 29 4 3 3 Profile 1 8 bit Outputs control 30 4 3 4 Profile 2 2 x 16 bit Inputs status 31 4 3 5 Profile 2 2 x 16 bit Outputs control 33 4 4 Acyclic data 34 4 4 1 Introduction 34 4 4 2 Data Types 34 4 4 3 List of parameters 36 4 4 4 Acyclic parameter channel for DX NET SWD3 48 4 4 5 SmartWire DT write resp...

Page 7: ...undamental technical principles is needed for commissioning In addi tion you should be familiar with the handling of the SmartWire DT system 0 2 Further manuals for this device Further information can be found in the following manuals On the topic Variable frequency drive DC1 MN04020003Z EN On SmartWire DT SmartWire DT The system MN05006002Z EN previous designation AWB2723 1617en SmartWire DT modu...

Page 8: ...ING Warns of the possibility of hazardous situations that could result in serious injury or even death DANGER Warns of hazardous situations that result in serious injury or death Indicates useful tips In order to make it easier to understand some of the images included in this manual the housing of the variable frequency drive as well as other safety relevant parts have been left out However it is...

Page 9: ...un clockwise rotating field GND Ground 0 V potential hex Hexadecimal base 16 numeral system ID Identifier unique ID LED Light Emitting Diode LED LSB Least significant bit MSB Most significant bit PE Protective earth PNU Parameter number REV Reverse run anticlockwise rotation field active ro Read Only read access only rw Read Write read write access SWD SmartWire DT UL Underwriters Laboratories Des...

Page 10: ...0 About this Manual 0 6 Units 6 DX NET SWD 06 13 MN04012009Z EN www eaton com ...

Page 11: ...09Z EN www eaton com 7 1 Device series 1 1 Checking the Delivery The packaging must contain the following parts a SWD interface card DX NET SWD3 a instructional leaflet IL040008ZU L Figure 1 Equipment supplied with the DX NET SWD3 interface card Ready I O A DX NET SWD3 ...

Page 12: ...e variable frequency drives of the PowerXL series Technical Data Symbol Unit Value General Standards meets the requirements of the EN 50178 standard for electrical safety Production quality RoHS ISO 9001 Environmental Conditions Operating Temperature ϑ C 40 no hoarfrost up to 70 Storage temperature ϑ C 40 85 Climatic proofing pw 95 relative humidity no condensation permitted Altitude H m max 1000 ...

Page 13: ...t DX NET SWD3 The following drawing shows the SmartWire DT interface card DX NET SWD3 Figure 3 Designations at DX NET SWD3 a Connection of SmartWire DT external device plug b SmartWire DT diagnostics LED c RJ45 plug d Clips for fixing to the variable frequency drive e Selector switch 1 0 A Ready I O A DX NET SWD3 ...

Page 14: ...ecting the DC1 variable frequency drive on the Smart Wire DT system and is intended for flush mounting in a machine of for assembly with other components for a machine or system Figure 4 Flush mounting in control panel L1 L L2 N L3 U V W 8 9 10 11 L1 L L2 N L3 U V W 8 9 10 11 L1 L L2 N L3 DC U DC BR 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 COM V W Ready I O A Ready I O A Ready off on ...

Page 15: ...you have a problem with your Eaton SmartWire DT interface card SWD3 When you call have following data ready the exact part no DX NET SWD3 the date of purchase an accurate description of the problem that has occurred in conjunction with the SmartWire DT interface card DX NET SWD3 Information concerning the guarantee can be found in the Terms and Conditions Eaton Industries GmbH 24 hour hotline 49 0...

Page 16: ...1 Device series 1 7 Disposal 12 DX NET SWD 06 13 MN04012009Z EN www eaton com ...

Page 17: ...the SmartWire DT system up to 99 modules can be connected to form a network Modules can include SmartWire DT I O modules or SmartWire DT modules for contactors soft starters drives or pilot devices The electrical connection is effected via a special 8 pole connecting lead and the relevant plugs Variable frequency drives of series DC1 with the SmartWire DT interface card SWD3 are suitable to be lin...

Page 18: ...lor Status Status signal Orange continuous light Switching command for variable frequency drive via SmartWire DT flashing Switching command active diagnostics available Green continuous light Device is ready error free flashing 1 Hz addressing process in progress after gateway control section power On after actuation of the configuration button on the gateway control section Module not in current ...

Page 19: ...ftware that runs under opera ting systems Windows 2000 SP 4 Windows XP Windows Vista 32 bit or Windows 7 and relieves you of the planning work required for an SWD topology The SmartWire DT interface card DX NET SWD3 can be used in the software SmartWire DT Assist from software version V 1 80 SmartWire DT gateway Firmware Version EU5C SWD CAN V 1 20 EU5C SWD DP V 1 20 The firmware of the SmartWire ...

Page 20: ...em you will not have to press the configuration button after replacing it and switching on the voltage The configuration button must only be pressed after replacing the interface card This ensures that the new interface card is assigned a net work address The SWD Assist program can be downloaded for free on the Internet at http downloadcenter moeller net DANGER Before replacing a DC1 variable freq...

Page 21: ...This chapter describes the mounting and electrical connection of the SmartWire DT interface card DX NET SWD3 Figure 5 Flush mounting of the interface card DX NET SWD3 Perform all installation work with the specified tools and without the use of excessive force L1 L L2 N L3 U V W 1 2 3 4 5 6 7 8 9 10 11 Ready I O A ...

Page 22: ...er as the search term 3 1 2 Notes on the mechanical surface mounting Figure 6 Perform mounting measures only in a de energized state DANGER The handling and installation tasks for the mechanical design and flush mounting of the SmartWire DT interface card DX NET SWD3 must only be carried out in a de energized state Wheninstalling the SmartWire DTinterface card DX NET SWD3 it is necessary to open t...

Page 23: ...d using the flat blade of a screw driver Figure 7 Removing the cover plugs Then the interface card DX NET SWD3 can be plugged on The module engages on the basic device with the two clips Figure 8 Plug on the interface card DX NET SWD3 Do not insert tools or other objects into the opened variable frequency drive Ensure that foreign bodies do not enter the opened housing wall L1 L L2 N L3 U V W 1 2 ...

Page 24: ... external device plug with the adapted ribbon cable Meaning 24 V DC Contactor control voltage Chassis ground Contactor control voltage GND for device supply voltage and data cable Data B Data cable B Data A Data cable A GND for device supply voltage and data data A data B SEL Select cable for automatic addressing of the SmartWire DT modules 15 V DC Device supply voltage NOTICE Do not install the S...

Page 25: ...conductor 3 4 2 Dismantling of DX NET SWD3 In order to dismantle the DX NET SWD3 interface card from the frequency inverter press on the left and right side of the fastening clips and pull this up carefully Then re insert both cover plugs in doing so note that the cover plugs are not identical Figure 12 Remove the DX NET SWD3 interface card NOTICE The dismantling must only be carried out with the ...

Page 26: ...3 Installation 3 4 Dismantling 22 DX NET SWD 06 13 MN04012009Z EN www eaton com ...

Page 27: ...an incorrect operating state The following parameter settings listed below are required for operation with SmartWire DT Valule P 12 Description 0 Control signal terminals 1 HMI device Keypad FWD 2 HMI device Keypad FWD REV 3 Modbus with internal ramp time 4 Modbus with ramp time via bus 5 PI controller with external actual value 6 PI controller with external actual value and totalized value of AI1...

Page 28: ...riate profile can be selected by the user 4 2 2 State diagrams The state diagrams used below correspond to PROFIdrive profile 4 1 and are adapted in line with the relevant profiles The grey boxes in the figures represent the current state S State with the help of the input bytes The white boxes represent the transition conditions with the help of the relevant output byte bits Dots are used to indi...

Page 29: ...h PNU 928 0 1 5 is used then the general state diagram shown below will apply The transitions will take place when the state of the EN_Set bit is changed Figure 14 State diagram Network S4 profile 1 S3 Switched On Bit 2 1 S4 Operation Bit 2 1 Bit 2 0 EN_Op Bit 2 1 EN_Op S4 1 Idle Operation Bit 3 0 Bit 4 0 S4 2 Ramping Up Operation Bit 3 1 Bit 4 0 S4 3 Ramping Down Operation Bit 3 1 Bit 4 0 S4 4 TO...

Page 30: ...on on the Ctl_Req and Ctl_PLC bits see Section 4 3 Cyclic data S1 Switching On Inhibited Bit 6 1 Bit 0 1 2 0 S2 Ready For Switching On Bit 0 1 Bit 1 2 6 0 S3 Switched On Bit 0 1 1 Bit 2 6 0 S4 Operation Bit 0 1 2 1 Bit 6 0 Standstill or Bit 3 0 EN_Op Standstill or Bit 3 0 EN_Op Bit 0 0 OnOff and Bit 1 1 Off2 and Bit 2 1 Off3 S5 Switching Off Quick Stop Bit 0 1 5 1 Bit 2 6 0 S5 Switching Off Ramp Stop B...

Page 31: ...Paused Operation Bit 8 1 Bit 10 0 S4 4 Ramping Down Operation Bit 8 1 Bit 10 0 S4 2 Ramping Up Operation Bit 8 1 Bit 10 0 S4 5 TOR Operation Bit 8 10 1 S4 1 Idle Operation Bit 8 10 0 Bottom of Ramp Top of Ramp Ramp Up Bit 4 1 EN_Ramp and Bit 5 1 Freeze and Bit 6 0 EN_Set Ramp Down Bit 4 1 EN_Ramp and Bit 5 1 Freeze and Bit 6 1 EN_Set Ramp Up Bit 4 0 EN_Ramp Bit 4 1 EN_Ramp and Bit 5 1 Freeze and B...

Page 32: ...and status data will be processed as per the I O link profile Profile 2 This group supplements the variable frequency drive profile with the PROFIdrive profile as the PNO has defined for the cyclic data exchange with a drive Control and status data will be processed according to the PROFIdrive profile Profile 2 is set in the default settings Table 5 Profiles Profile Input bytes status Output bytes...

Page 33: ...ive operation 4 DIAG 0 no diagnostic alarm 1 Diagnostic alarm present 5 Not used 6 PRSNT 0 Device not present 1 Device present 7 SUBST 0 Configured module present 1 Universal module M22 SWD NOP C present 1 0 ERR Error present 0 no error 1 Error 1 WARN Warning present 0 no warning 1 Warning 2 RDY Ready switched on 0 not switched on 1 switched on 3 f f ref Running at setpoint 0 Ref frequency not rea...

Page 34: ...aning 0 0 FWD Start anticlockwise operation 1 REV Start Reverse 2 EN_Op Operation released 0 Stop immediate disconnection of the output 1 Operation 3 FaultAck Fault Acknowledge 0 Do not acknowledge current fault 1 Acknowledge current fault rising edge 0 1 4 I1 Programmable Input 1 Default settings fixed frequency 5 I2 Programmable Input 2 Default settings fixed frequency 6 I3 Programmable Input 3 ...

Page 35: ...ured module present 1 universal module M22 SWD NOP C present 1 2 0 RSO Ready For Switching On S2 0 Not ready for switching on 1 Ready for switching on 1 RDY Ready to operate switched on S3 0 not ready for operation 1 ready for operation 2 EN Enabled operation S4 0 Stop 1 Operation 3 ERR Error present 0 no error 1 Error 4 C_Stop Free run down output de energized coast stop 0 no free run down 1 free...

Page 36: ...g threshold 0 Actual speed is less than or equal to the signaling threshold 1 Actual speed is greater than the signaling threshold 11 Q 1 Device Info Q1 12 Q2 Device Info Q2 13 Q3 Device Info Q3 14 Q4 Device Info Q4 15 Q5 Device Info Q5 3 4 0 15 ActSpeed Current speed in percent from 200 to 200 100 4000hex Byte BIT Designation Meaning ...

Page 37: ...he motor with the ramp function 0 Do not activate setpoint value 1 activate setpoint value 7 FaultAck Fault Acknowledge 0 Do not acknowledge current fault 1 Acknowledge current fault rising edge 0 1 8 Jog 1 Jog with setpoint value 1 9 Jog 2 Jog with setpoint value 2 10 Ctl_PLC PLC assumes control Control by PLC 0 no control via PLC 1 Control via PLC 11 I1 programmable input 1 12 I2 programmable in...

Page 38: ...nication The data types used here are specified in the following 4 4 2 1 PROFIdrive specific N2 normalized value N2 normalized value for a relative scaling N2 is in the range of 200 to 200 0 is equivalent to 0 0x0 100 is equivalent to 212 0x4000 The representation is carried out in two complements the most significant bit MSN is the first bit after the unsigned bit SN of the first octet SN 0 posit...

Page 39: ...ndard data types The most important data types are listed in the following Coding Value Range Resolution Length 118 0 i 32767 Ta Ta 2 octets Coding Value Range Resolution Length 120 0 i 2 2 14 Ta 2 14 Ta 2 octets Data types used in the PROFIdrive profile Reference Coding Integer8 Integer8 see IEC 61158 5 2003 2 Integer16 Integer16 see IEC 61158 5 2003 3 Integer32 Integer32 see IEC 61158 5 2003 4 U...

Page 40: ...ls in Volt 24 0 rw U16 Adaptation frequency U f characteristic curve P 29 0 P 09 Details in Hz 27 0 rw U16 Boost P 11 FS1 0 200 FS2 0 150 FS3 0 100 100 10 28 0 rw Boost frequency P 32 Only available with alternating current motor types 29 0 rw Boost time P 33 Only available with alternating current motor types 111 0 rw T2 Acceleration ramp time P 03 0 600 0 6000 300 3 00 s 114 0 rw T2 Deceleration...

Page 41: ...0 0 10 V 1 0 20 mA 2 t4 20 mA 3 r4 20 mA 4 t20 4 mA 5 r20 4 mA 261 1 rw U16 Analog input scaling P 35 0 5000 100 10 262 1 rw U16 Analog input compensation P 39 5000 5000 300 30 0 310 0 rw UInt16 Profile used 0 11 0 Communication lost 10 PROFIdrive profile 11 8 bit profile 320 1 rw U16 Access codes for the extended menu P 14 0 9999 320 0 rw U16 Extendedparameter menu access code P 37 0 9999 Definit...

Page 42: ...ching frequency P00 14 0 5 0 4 kHz 1 8 kHz 2 12 kHz 3 16 kHz 4 24 kHz 5 32 kHz 423 0 rw U16 Digital input function selection P 15 0 12 see table Input functions 451 0 rw U16 Selection of the relay output func tion P 18 0 7 0 RUN enable FWD REV 1 READY ready for operation 2 output frequency frequency reference value 3 Error message variable frequency drive not ready 4 Output frequency limit value P...

Page 43: ...y 4 Output frequency limit value P 19 5 Output current limit value P 19 6 Output limit value P 19 7 Output current limit value P 19 8 Output frequency f Out 0 100 fmax P 01 9 Output current 0 200 Ie P 08 501 1 ro UInt16 Motor voltage P00 07 0 500 501 1 ro UInt16 DC link voltage P00 08 0 1000 550 0 ro Int8 Status of digital input P00 04 0 255 560 0 ro U16 Analog input 1 P00 01 0 1000 500 50 0 560 1...

Page 44: ...e 4 Auto_3 Will start automat ically 3 times 5 Auto_4 Will start automati cally four times 6 Auto_5 Will start automati cally five times 620 3 rw U16 Drive start function Scanning mode P 31 0 3 REAF start function with auto matic restart operating unit This parameter will only be active if the keypad control operating mode is being used P 12 1 or 2 0 Minimum speed keypad 1 Previous speed keypad 2 ...

Page 45: ...ts warning bit Device keeps running 2 Stop with ramp Sets error bit 3 Stop with 2nd ramp Sets error bit 4 Switches energy off Sets error bit 850 0 ro U16 Motor current log P00 17 0 newest value 850 1 ro U16 850 2 ro U16 100 10 0 A 850 3 ro U16 850 4 ro U16 850 5 ro U16 850 6 ro U16 850 7 ro U16 oldest value 852 0 ro U16 DC bus voltage log P00 15 0 1200 newest value 852 1 ro U16 852 2 ro U16 852 3 ...

Page 46: ...s 950 1 ro UInt16 Error per error situation 952 0 ro UInt16 Situation memory error 962 0 ro TimeDiff4 fixed to 10 ms 10 Basis for all T parameters 964 0 ro UInt16 Device identification 4Dhex 964 1 ro UInt16 Device Type 0Chex 964 2 ro UInt16 Software version 0 65535 964 3 ro UInt16 Firmware Date Year 0 65535 964 4 ro UInt16 Firmware date 0 65535 TTMM decimal 964 5 ro UInt16 Object Number 0 65535 96...

Page 47: ...igital reference P 45 0 1000 100 10 0 2112 0 rw U16 PI return selection P 46 0 3 0 Analog input 2 1 Analog input 1 2 Motor current 2123 0 rw U16 PI operation mode P 43 0 1 0 direct operation 1 Inverted operation 2131 0 rw UInt16 PI feedback wake up level P 49 0 1000 900 90 0 2204 0 rw U16 Brake switching enable P 34 0 2 Brake chopper activation only for FS2 and FS3 0 locked 1 enabled with overload...

Page 48: ...rolled in both the forward and reverse directions if an external or remote control keypad is used The keypad can be used to switch between a clockwise rotating field FWD and a clockwise rotating field REV by pressing the START pushbutton 3 Modbus Control via Modbus RTU RS485 with the internal acceleration deceleration ramps 4 Modbus Control via Modbus RTU RS485 port the acceleration deceleration r...

Page 49: ...Wire DT Local setpoint value P 15 for local settings 3 Local control commands setpoint values via SmartWire DT DI1 Start Stop 4 Actuation via SmartWire DT depending on the settings with the loss in communication automatic change to the local actuation 5 Control commands and setpoint values via SmartWire DT Also via DI1 enable and via DI2 enable setpoint Parameter 1 to 5 of PNU 928 are equivalent t...

Page 50: ...og input 1 and 2 5 0 Blocked 1 Start enable FWD 0 Blocked 1 Start enable REV 0 Selected setpoint source 1 Fixed frequency 1 P 20 Setpoint value AI1 Connection of DI1 and DI2 leads to a quick stop P 24 6 0 Blocked 1 Start enable 0 FWD 1 REV External fault 0 Fault 1 Enable Setpoint value AI1 Connection of an external thermistor of type PT100 or similar to DI3 7 0 Blocked 1 Start enable FWD 0 Blocked...

Page 51: ... Motor thermal overload 5400 PS trP Internal fault power section 3210 O_Vo I Overvoltage DC link 3220 V_Vo I Undervoltage DC link 4230 O Overtemperature heat sink 4220 V Undertemperature heat sink 6300 P dEF Default settings parameters have been loaded 9000 E triP external error message 7510 SC trP Field bus error 5130 reserved 3130 P LOSS Phase failure mains side 2213 SPIn F Motor pick up control...

Page 52: ...is used to define whether the job is a read or a write job After the write request is transmitted contains read or write job a write response without data will be expected Then the coordinator poles through the read request of the variable fre quency drive prompted by the application of the higher level PLC This keeps acknowledging the read request as negative Error State Conflict until the read r...

Page 53: ...ation number for each new request in the application They are ten mirrored by DC1 variable frequency drive 01hex FFhex i e 1dec 255dec 1 Request ID Request ID The type of request is specified here 01hex Read request 2 DO ID Drive Object ID 00hex 3 No of Paramters Number of parameters Only individual parameter processing is supported 01hex 4 Attribute Attribute Defines which object type should be a...

Page 54: ...dec 1 Request ID Request ID The type of request is specified here 02hex Write job 2 DO ID Drive Object ID 00hex 3 No of Paramters Number of parameters Only individual parameter processing is supported 01hex 4 Attribute Attribute Defines which object type should be accessed 10hex 16dez Value 5 No of Elements Number of elements Address of the parameter that should be accessed PNU 0 up to PNU 999 00h...

Page 55: ... requested 4 4 5 2 SmartWire DT read response The SmartWire DT read request will be acknowledged until there is a SmartWire DT read response The following SmartWire DT read responses are possible SmartWire DT read response Error If there is an error related to addressing index the DC1 variable frequency drive is not available if the response from the DC1 variable frequency drive is still pending S...

Page 56: ...x 23hex Fault number hex Designation Description Supplemen tary infor mation DC1 00 Invalid parameter number Attempting to access a non available parameter 0 01 Parameter value cannot be changed Attempting to have write access to a parameter that cannot be modified Subindex 02 Value below lower limit or above upper limit Attempting to have write access with a value outside the value range Subindex...

Page 57: ... address not permissible Not permissible or non supported value for attribute No of elements parameter number subindex or a combination thereof 0 17 Format not permissible Write request Invalid format or format not permissible for this parameter 0 18 No of values are not consistent Write request The number ofvalues in the parameter data does not match the number of values for the parameter address...

Page 58: ...O ID Drive Object ID Is echoed 3 No of Parameters Number of parameters 01hex Byte Designation Description 0 Request Reference Request identification Is echoed 1 Response ID Response ID 01hex Read job 2 DO ID Drive Object ID Is echoed 3 No of Parameters Number of parameters 01hex 4 Format Format 01hex 7Chex i e 01dez 124dez 5 No of Values Number of values 01hex value 6 9 Value Value Specifies the v...

Page 59: ... PROFIBUS DP gateway EU5C SWD DP As a result the parameter channel can be used in a fully transparent manner by SmartWire DT modules The following diagram shows the protocol between the PROFIBUS DP master PROFIBUS DP gateway and a DC1 variable frequency drive Figure 18 Acyclic PROFIBUS DP parameter channel protocol For more information on the subject of the transfer of acyclic data consult the MN0...

Page 60: ... error code 54dec representing the errors listed above can be output via function blocks XDPMV1_READ and XDPMV1_WRITE when using a PROFIBUS DP master Error Type Failure code Description Error_Code_1 A1hex Write error Only reading allowed for indexes 1 3 PKE motor protective circuit breaker Error_Code_1 A2hex DC1 variable frequency drive is not available Error_Code_1 B0hex There is no valid index E...

Page 61: ...diagnostic in the cyclic profile with input byte 0 bit 4 DIAG A device response if any will be described in the advanced diagnostics In addition in all profiles the following bits ERR the variable frequency drive stops or WARN no reaction of the variable frequency drive in the corresponding input bytes are used to show whether there are any diagnostic messages i e errors or warnings After the caus...

Page 62: ...cation problem in the DC1 vari able frequency drive If the error continues switch the supply voltage off on Check EMC Replace soft starter 15 no unambiguous position of the 1 0 A switch for more than 4 seconds Move the 1 0 A switch to one of the three defined positions Input byte 0 bit field 2 3 A1 A2 is used to signal a value of 00hex For more information see below 19 There is a warning at hand f...

Page 63: ...he acyclic parameter channel of the relevant bus system The ERR and WARN bits in corresponding input bytes 4 to 11 are used to show whether there are any diagnostic messages present i e errors or warnings You can acknowledge faults ERR as follows Profile FaultAck 1 Warnings WARN cannot be acknowledged since they are simply messages without an ensuing response the DC1 variable frequency drives Avai...

Page 64: ...4 Commissioning 4 5 SmartWire DT diagnostics 60 DX NET SWD 06 13 MN04012009Z EN www eaton com ...

Page 65: ...DX NET SWD3 interface card Figure 20 Variable frequency drive DC1 in FS1 with SmartWire DT connection Ready A O I 43 mm 1 69 34 mm 1 34 20 mm 0 79 38 mm 1 5 VAR EMC 1 2 3 4 5 6 7 8 9 10 11 6 mm 0 24 12 mm 0 47 Ready A O I 81 mm 50 mm 3 19 1 97 144 mm 5 67 156 8 mm 6 17 4 mm 0 16 7 mm 0 28 170 mm 184 mm 6 9 7 24 ...

Page 66: ...2009Z EN www eaton com Figure 21 Variable frequency drive DC1 in FS2 with SmartWire DT connection VAR EMC 1 2 3 4 5 6 7 8 9 10 11 6 mm 12 mm 0 47 0 24 215 mm 8 46 231 mm 9 09 8 mm 0 31 107 mm 4 21 75 mm 2 95 172 mm 6 77 5 mm 0 2 Ready A O I 184 8 mm 7 28 ...

Page 67: ...ive DC1 in FS3 with SmartWire DT connection 5 2 SmartWire DT Figure 23 SmartWire DT flat band conductor DC BR U V W L2 N L3 DC L1 N 1 2 3 4 5 6 7 8 9 10 11 EMC VAR 6 mm 12 mm 0 47 0 24 131 mm 6 16 100 mm 3 94 255 mm 10 04 273 mm 10 75 8 5 mm 0 33 195 mm 7 68 207 8 mm 8 18 5 mm 0 2 Ready A O I SWD4 8SF2 5 15V ...

Page 68: ...5 Appendix 5 2 SmartWire DT 64 DX NET SWD 06 13 MN04012009Z EN www eaton com ...

Page 69: ...F Fieldbus description files 15 FS frame size size 5 FWD forward run clockwise rotation field 5 G Gateways 15 GND ground 5 H Hotline 11 I Installation 17 K Key to part numbers 8 L LCD 5 M Maintenance 11 N Notes on mechanical surface mounting 18 On the documentation 18 P Parameter channel acyclic 48 Parameter request 48 Part no 8 PE 5 PNU parameter number 5 49 PROFIdrive 24 48 Protective earth 5 R ...

Reviews: