4 Commissioning
4.3 Cyclic data
DX-NET-SWD
06/13 MN04012009Z-EN
www.eaton.com
33
4.3.5 Profile 2 (2 x 16 bit): Outputs (control)
Output bytes 0 and 4 are mapped as follows on SmartWire-DT.
Table 9:
Profile 11: Output bytes 0 and 4
Word
BIT
designation
Meaning
0
0
OnOff
On/Off
0: Normal stop (with configured ramp time)
1: Operation
1
Off2
Run-down (Coast Stop: Off 2)
0: Coast stop (switch off output voltage)
1: no free run-down
2
Off3
Quick Stop: Off3
0: Quick stop (shortest ramp)
1: no quick stop
3
EN_Op
Operation released
0: Stop
1: Operation
4
EN_Ramp
Release ramp (Enable Ramp Generator)
0: Reset ramp (setpoint value = 0)
1: Release ramp
5
Unfreeze
Unfreeze ramp
0: Freeze ramp (the ramp generator's current output value will be
frozen)
1: Do not freeze ramp
6
EN_Set
Activate setpoint value:
EN_Set enables the setpoint value and starts or stops the motor
with the ramp function.
0: Do not activate setpoint value
1: activate setpoint value
7
FaultAck
Fault Acknowledge
0: Do not acknowledge current fault
1: Acknowledge current fault (rising edge: 0
→
1)
8
Jog 1
Jog with setpoint value 1
9
Jog 2
Jog with setpoint value 2
10
Ctl_PLC
PLC assumes control (Control by PLC)
0: no control via PLC
1: Control via PLC
11
I1
programmable input 1
12
I2
programmable input 2
13
I3
programmable input 3
14
I4
programmable input 4
15
ExtFault
External Fault
If the bit is set, the DC1 variable frequency drive will stop with a
selected PNU 840 function. The behavior is the same as if there
were a change from 1
→
0 in the Enable signal, with the exception
that the variable frequency drive soft starter will switch to the Error
status (input bytes n + 4: bit 3). The external fault can be reset just
like any other fault (with Fault acknowledge (bit 7) or by switching
the supply voltage off and on).
0: no external fault
1: external fault
1
0 - 15
Setpoint
setpoint input in percent from -100 % to + 100 %;
100 %
≙
4000
hex
Summary of Contents for PowerXL DX-NET-SWD
Page 4: ...II ...
Page 10: ...0 About this Manual 0 6 Units 6 DX NET SWD 06 13 MN04012009Z EN www eaton com ...
Page 16: ...1 Device series 1 7 Disposal 12 DX NET SWD 06 13 MN04012009Z EN www eaton com ...
Page 26: ...3 Installation 3 4 Dismantling 22 DX NET SWD 06 13 MN04012009Z EN www eaton com ...
Page 64: ...4 Commissioning 4 5 SmartWire DT diagnostics 60 DX NET SWD 06 13 MN04012009Z EN www eaton com ...
Page 68: ...5 Appendix 5 2 SmartWire DT 64 DX NET SWD 06 13 MN04012009Z EN www eaton com ...