4 Commissioning
4.4 Acyclic data
DX-NET-SWD
06/13 MN04012009Z-EN
www.eaton.com
43
975
5
ro
UInt16
class info
1
Do not read-out
975
6
ro
UInt16
Supports Application Class
1
976
0
rw
UInt16
2100
0
rw
U16
PI proportional gain
P-41
1 - 300
10
≙
1.0
2101
0
rw
U16
PI integral time constant
P-42
0 - 300
10
≙
1.0 s
2110
0
rw
U16
Selection of the PI reference of
the user
P-44
0 - 1
0 : Preset digital setpoint value
1: Analog input 1
2111
0
rw
U16
PI digital reference
P-45
0 - 1000
100
≙
10.0 %
2112
0
rw
U16
PI return selection
P-46
0 - 3
0: Analog input 2
1: Analog input 1
2: Motor current
2123
0
rw
U16
PI operation mode
P-43
0 - 1
0: direct operation
1: Inverted operation
2131
0
rw
UInt16
PI feedback wake up level
P-49
0 - 1000
900 = 90.0 %
2204
0
rw
U16
Brake switching enable
P-34
0 - 2
Brake chopper activation
(only for FS2 and FS3)
0 : locked
1: enabled with overload
protection braking resistance
2: enabled with overload
protection braking resistance
2221
0
rw
U16
DC injection at stop
P-32
0 - 250
250
≙
25.0 s
PN
U index
PN
U subindex
Access
right
Data
type
Meaning
Display
number
Value Range
Description
Summary of Contents for PowerXL DX-NET-SWD
Page 4: ...II ...
Page 10: ...0 About this Manual 0 6 Units 6 DX NET SWD 06 13 MN04012009Z EN www eaton com ...
Page 16: ...1 Device series 1 7 Disposal 12 DX NET SWD 06 13 MN04012009Z EN www eaton com ...
Page 26: ...3 Installation 3 4 Dismantling 22 DX NET SWD 06 13 MN04012009Z EN www eaton com ...
Page 64: ...4 Commissioning 4 5 SmartWire DT diagnostics 60 DX NET SWD 06 13 MN04012009Z EN www eaton com ...
Page 68: ...5 Appendix 5 2 SmartWire DT 64 DX NET SWD 06 13 MN04012009Z EN www eaton com ...