4 Commissioning
4.4 Acyclic data
DX-NET-SWD
06/13 MN04012009Z-EN
www.eaton.com
45
Parameter PNU 928 has 6 functions:
Value
Description
0
Control signal terminals (I/O)
The variable frequency drive will respond directly to signals applied to the control signal
terminals.
1
Control commands and setpoint values via SmartWire-DT
DI1 = Hardware enable, P-15: no function
2
Control commands via SmartWire-DT
Local setpoint value (P-15 for local settings)
3
Local control commands, setpoint values via SmartWire-DT (DI1 = Start / Stop)
4
Actuation via SmartWire-DT - depending on the settings with the loss in communication,
automatic change to the local actuation
5
Control commands and setpoint values via SmartWire-DT.
Also via DI1 enable and via DI2 enable setpoint
→
Parameter 1 to 5 of PNU 928 are equivalent to the parameters
9-13 from P-12. Parameter 0 of the PNU 928 contains parame-
ters 1 to 8 from P-12. That is what the parameter value of P-12
looks like between 0 and 8 for the PNU 928 such as 0.