4 Commissioning
4.4 Acyclic data
52
DX-NET-SWD
06/13 MN04012009Z-EN
www.eaton.com
SmartWire-DT read re) – Parameter channel error
If there is an error in the parameter channel, a positive SmartWire-DT read
re) – Parameter channel error will be generated. The error will be
contained either in a write job or a read job.
The following table lists the PROFIdrive profile’s parameter channel errors.
The possible errors for the DC1 variable frequency drive are marked
(column
DC1
).
Table 11:
Parameter channel errors with PROFIdrive
Byte
Designation
Description
0
Request Reference
Request identification: Is echoed
1
Response-ID
Response ID: 81
hex
: Read job(-); 82
hex
: Write job(-)
2
DO-ID
Drive-Object-ID: Is echoed
3
No. of Parameters
Number of Parameters: 01
hex
4
Format
Format: 44
hex
: Error
5
No. of Values
Number of values: 01
hex
6 - 9
Error Number
Fault number: 00
hex
– 23
hex
Fault-
number
[hex]
Designation
Description
Supplemen-
tary infor-
mation
DC1
00
Invalid parameter number
Attempting to access a non-available
parameter
0
✓
01
Parameter value cannot be
changed
Attempting to have write access to a
parameter that cannot be modified
Subindex
✓
02
Value below lower limit or above
upper limit
Attempting to have write access with a
value outside the value range
Subindex
✓
03
Bad subindex
Attempting to access to a non-available
subindex in a string or array parameter
Subindex
✓
04
Not an array
Attempting to use a subindex in order to
access a parameter without index
0
05
Incorrect data type
Attempting to access a parameter with
a value not corresponding to the
parameter’s data type
0
✓
06
Setting not allowed
Write access with a non-zero value not
allowed
Subindex
✓
07
Description element cannot be
modified
Attempting to have write access to a
description element that cannot be
modified
Subindex
08
reserved
–
–
09
No description data available
Attempting to access a non-available
description. The value is not available.
0
✓
Summary of Contents for PowerXL DX-NET-SWD
Page 4: ...II ...
Page 10: ...0 About this Manual 0 6 Units 6 DX NET SWD 06 13 MN04012009Z EN www eaton com ...
Page 16: ...1 Device series 1 7 Disposal 12 DX NET SWD 06 13 MN04012009Z EN www eaton com ...
Page 26: ...3 Installation 3 4 Dismantling 22 DX NET SWD 06 13 MN04012009Z EN www eaton com ...
Page 64: ...4 Commissioning 4 5 SmartWire DT diagnostics 60 DX NET SWD 06 13 MN04012009Z EN www eaton com ...
Page 68: ...5 Appendix 5 2 SmartWire DT 64 DX NET SWD 06 13 MN04012009Z EN www eaton com ...