4 Commissioning
4.3 Cyclic data
DX-NET-SWD
06/13 MN04012009Z-EN
www.eaton.com
31
4.3.4 Profile 2 (2 x 16 bit): Inputs (status)
Input bytes 0 to 4 are mapped as follows on SmartWire-DT.
Table 8:
Profile 11: Input bytes 0 to 4
Byte
BIT
Designation
Meaning
0
0, 1
–
Not used
2, 3
A1, A2
1-0-A-switch on DX-NET-SWD3:
00: not defined
10: Position A: Automatic (commands via SmartWire-DT/
control signal terminal)
01: Position 0: variable frequency drive stop
11: Position 1: variable frequency drive operation
4
DIAG
0: no diagnostic alarm
1: Diagnostic alarm present
5
–
Not used
6
PRSNT
0: Device not present
1: Device present
7
SUBST
0: Configured module present
1: universal module M22-SWD-NOP(C) present
1, 2
0
RSO
Ready For Switching On: S2
0: Not ready for switching on
1: Ready for switching on
1
RDY
Ready to operate; switched on: S3
0: not ready for operation
1: ready for operation
2
EN
Enabled; operation: S4
0: Stop
1: Operation
3
ERR
Error present
0: no error
1: Error
4
C_Stop
Free run-down, output de-energized (coast stop)
0: no free run-down
1: free run-down
5
Q_Stop
Quick stop, shortest ramp
0: no quick stop
1: Quick stop
6
SOI
Reclosing lockout (switching on inhibited: S1)
0: No switch-on inhibit
1: Switch-on inhibit
7
WARN
Warning present:
0: no warning
1: Warning
8
f = f-ref
operation at setpoint
0: Ref. frequency not reached
1. Ref. frequency reached
9
Ctl_Req
Control requested to PLC
Is set if PNU 928.0 = 1 - 5.
0: Not ready for remote control
1: Ready for remote control
Summary of Contents for PowerXL DX-NET-SWD
Page 4: ...II ...
Page 10: ...0 About this Manual 0 6 Units 6 DX NET SWD 06 13 MN04012009Z EN www eaton com ...
Page 16: ...1 Device series 1 7 Disposal 12 DX NET SWD 06 13 MN04012009Z EN www eaton com ...
Page 26: ...3 Installation 3 4 Dismantling 22 DX NET SWD 06 13 MN04012009Z EN www eaton com ...
Page 64: ...4 Commissioning 4 5 SmartWire DT diagnostics 60 DX NET SWD 06 13 MN04012009Z EN www eaton com ...
Page 68: ...5 Appendix 5 2 SmartWire DT 64 DX NET SWD 06 13 MN04012009Z EN www eaton com ...