4 Accessories
4.7 Device-specific accessories for devices with an IP20 degree of protection
100
DC1-S…20…, DC1-S…OE1 Variable Frequency Drives
05/21 MN040058EN
www.eaton.com
4.7.2 DXC-EXT-2RO output expansion
Figure 68: DXC-EXT-2RO
Expansion module DXC-EXT-2RO can be used to convert digital output DO1
(control signal terminals 8 and 9) on DC1-S… variable frequency drives to a
dry relay output K2 (N/O). When this option is used, the variable frequency
drive will have two dry relay outputs available and will be able to switch
voltages of up to 250 V AC and 220 V DC.
Table 23: DXC-EXT-2RO connection terminals
Connection
terminal
Signal
Description
Default Setting
1
+24V
Control voltage for the
digital inputs
100 mA max.
Reference potential: 0 V
(terminal 7)
–
2
DI1
Digital Input 1
8 - 30 V = HIGH, R
i
> 6 k
Ω
FWD
3
DI2
Digital input 2
8 - 30 V = HIGH, R
i
> 6 k
Ω
Select Quick-Dec
4
AI2/DI3
Analog input 2 or digital
input 3
analog:
0 - 10 V, R
i
> 72 k
Ω
0/4 - 20 mA, R
B
= 500
Ω
digital:
8 - 30 V = HIGH, R
i
> 72 k
Ω
Select AI1REF/f-Fix1
5
+10 V
Reference voltage
10 mA max.
Reference potential: 0 V
(terminal 7)
–
6
AI1/DI4
Analog input 1 or digital
input 4
analog:
0 - 10 V, R
i
> 72 k
Ω
0/4 - 20 mA, R
B
= 500
Ω
digital:
8 - 30 V = HIGH, R
i
> 72 k
Ω
AI1 REF
(analog, 0 - 10 V)
7
0 V
Common reference potential for all digital and analog inputs
and outputs
–
8
K23
Relay RO2
(normally open)
250 V, 1 A AC/220 V, 1 A DC
Output Frequency
(analog, 0 - 10 V)
9
K24
Relay RO2
(normally open)
250 V, 1 A AC/220 V, 1 A DC
–
10
K13
Relay RO1
(normally open)
250 V, 6 A AC/30 V, 5 A DC
RUN, enable signal for
device activated
11
K14
1 2 3 4 5 6