1.4
Options and Accessories
Contact an Eaton sales representative for information about the following options.
1.4.1
Integrated Battery Cabinets
Battery backup protection can be provided by equipping the UPS system with
9395P-600 battery cabinets containing sealed lead‐acid, maintenance‐free batteries.
The cabinets are designed for
standalone
installation and may be installed adjacent to
the UPS or in a separate location. The recommended installation location for adjacent
battery cabinets is on the right side of the UPS cabinet to allow for future expansion
using an external module.
Consult the .
Eaton Power Xpert 9395 Integrated Battery Cabinet (Model 1085 and
1085HR) Installation Manual (P-164000580)
for specifics on battery cabinet usage
with the 9395P-600.
1.4.2
Field Installed UPM
A Field Installed UPM (FI-UPM) provides redundancy for the 9395P-600. The FI-UPM
may be installed at any time in the future. The module cabinet is installed on the left
side of the ISBM section and is wired directly to the UPS. No input or output wiring
changes are needed for adding redundancy. Operation remains the same as the
original UPS.
Refer to the
Eaton Power Xpert 9395P UPS Field Installed UPM Mechanical
Installation Manual (P-164000503)
for specifics on the FI-UPM usage with the
9395P-600.
1.4.3
Sync Control
An optional 9395P-600 Sync Control maintains the critical load outputs of two
separate single module 9395P-600 UPS systems in synchronization. This option
facilitates the uninterrupted transfer of the load from one load bus to another by
means of transfer switches. The Sync Control is housed in a wall‐mounted panel that
can be located between the UPS units for easy wiring.
Refer to the
Eaton Power Xpert 9395P Sync Control Installation and Operation Manual
(P164000502)
for specifics on sync control usage with the 9395P-600.
1.4.4
Single-Feed Kit
An optional kit is available for converting the dual-feed rectifier and bypass inputs to a
single-feed configuration. The kit consists of jumpers and bus bar extensions for each
phase, and the hardware required for installation.
Refer to the
Eaton 9395/9395P UPS (1000-1200 kVA) Single-Feed Kit Installation
Instructions (P-164000610)
manual for installation instructions.
1.4.5
Distributed Bypass System
There are two types of redundancy: UPS based (based on the number of UPSs) and
UPM based (based on the number of UPMs).
NOTE
All UPSs in the distributed bypass system must contain the same number of UPMs. Mixed UPS kVA
ratings are not permitted.