UPS INSTALLATION PLAN AND UNPACKING
Eaton
Power Xpert 9395P-600 (380V-600V) UPS Installation and Operation Manual
S
P-164000710 Rev 1
www.eaton.com/powerquality
3-37
Table 3‐25. 415V Power Cable Conduit Recommendations
UPS Model
Voltage
Terminal
Number of Wires
in Conduit
Minimum Conduit
Trade Size (in.)
Number of
Conduits
Eaton 9395P-600/550
415 Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
4
3
4
AC Input to Bypass and Output
(A, B, C, Ground)
5
3
3
Eaton 9395P-600/500
415 Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
4
3
4
AC Input to Bypass and Output
(A, B, C, Ground)
5
3
3
Eaton 9395P-600/450
415 Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
4
3
3
AC Input to Bypass and Output
(A, B, C, Ground)
5
3
3
Eaton 9395P-600/400
415 Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
4
3
3
AC Input to Bypass and Output
(A, B, C, Ground)
5
3
3
Eaton 9395P-600/300
415 Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
4
3
2
AC Input to Bypass and Output
(A, B, C, Ground)
5
3
2
DC (same for all ratings)
Battery
(Positive, Negative, Ground)
See Note 1
NOTE 1
Select conduit taking into consideration the DC input wire sizes and terminations listed in appropriate Tables, type of battery installation, and
requirements from NEC Table 4, Electrical Metallic Tubing (EMT).
NOTE 2
Bypass conduit data is not applicable to IOM configurations.
Battery Cable Routing: