UPS INSTALLATION PLAN AND UNPACKING
Eaton
Power Xpert 9395P-600 (380V-600V) UPS Installation and Operation Manual
S
P-164000710 Rev 1
www.eaton.com/powerquality
3-40
Table 3‐28 lists the recommended rating for 600V, 575V, 480V, 415V, 400V, and 380V
input circuit breakers with 100% breaker ratings for rectifier input.
Table 3‐28. Recommended Input Circuit Breaker Ratings 100%
UPS Model
Output kW
600V/575V
480V
415V
400V
380V
Eaton 9395P-600/600
800A
1000A
1000A
1000A
1000A
Eaton 9395P-600/550
Eaton 9395P-600/500
600A
800A
800A
800A
800A
Eaton 9395P-600/450
600A
700A
700A
700A
700A
Eaton 9395P-600/400
500A
600A
600A
600A
600A
Eaton 9395P-600/300
Eaton 9395P-600/275
Eaton 9395P-600/250
Eaton 9395P-600/225
Eaton 9395P-600/200
See Note
400A
1000A
1000A
1000A
1000A
NOTE
Bypass breakers are not required for IOM configurations.
C
A
U
T
I
O
N
To reduce the risk of fire, connect only to a circuit provided with maximum input circuit breaker current
ratings from Table 3‐28 in accordance with the NEC, ANSI/NFPA 70.
MISE EN GARDE!
Pour réduire le risque d’incendie, ne brancher qu’à un circuit avec le courant nominal maximal du disjoncteur
d’entrée indiqué dans le tableau 3-28 conformément à la norme ANSI/NFPA 70 du NEC.
The line‐to‐line unbalanced output capability of the UPS is limited only by the full load
per phase current values for AC output to critical load shown in Table 3‐6 to
Table 3‐17. The recommended line‐to‐line load unbalance is 50% or less.
Bypass and output overcurrent protection and bypass and output disconnect switches
are to be provided by the customer. Module Output Breakers (MOBs) are to be
provided by the customer.
Table 3‐29 lists the recommended rating for 600V, 575V, 480V, 415V, 400V, and
380V bypass, output, and MOB circuit breakers with 100% breaker rating. Bypass
breakers are not applicable for IOM configurations.