UPS SYSTEM INSTALLATION
Eaton
Power Xpert 9395P-600 (380V-600V) UPS Installation and Operation Manual
S
P-164000710 Rev 1
www.eaton.com/powerquality
4-17
4.
Locate the external wiring terminal hardware kit packed on the bottom left side
of the ISBM section.
5.
Using hardware from the external wiring terminal hardware kit (see Table 3‐20),
connect phase A, B, and C rectifier input power wiring from the utility source to
the rectifier input terminals in the ISBM section. See paragraph 3.2.5 for wiring
and termination requirements.
6.
If installing a UPS configured as an Input Output Module (IOM), proceed to
Step 8; otherwise, proceed to Step 7.
7.
Using hardware from the external wiring terminal hardware kit (see Table 3‐20),
connect phase A, B, and C bypass input power wiring from the utility source to
the bypass input terminals in the ISBM section. See paragraph 3.2.5 for wiring
and termination requirements.
8.
If wiring a distributed bypass system, proceed to Step 9; otherwise, proceed to
Step 11.
9.
Using hardware from the external wiring terminal hardware kit (see Table 3‐20),
connect phase A, B, and C wiring from the output terminals of each UPS unit to
the customer-supplied tie cabinet or load distribution panel. See paragraph 3.2.5
for wiring and termination requirements.
10.
11.
Using hardware from the external wiring terminal hardware kit (see Table 3‐20),
connect phase A, B, and C power wiring from output terminals to the critical
load. See paragraph 3.2.5 for wiring and termination requirements.
12.