Table 3‐19. Supplied Intercabinet Wiring Terminal Hardware Kit
Part
Size
Quantity
Terminals Used On
Eaton Part Number
Flat Washer
M8
36
UPM AC Input, UPM Battery Input, UPM AC
Output
180500036-080
Conical Washer
M8
36
UPM AC Input, UPM Battery Input, UPM AC
Output
180500037-080
Nut
M8
36
UPM AC Input, UPM Battery Input, UPM AC
Output
180200001-05
Terminals E1 through E11 are 2‐hole busbar mountings for standard NEMA 2‐hole
barrel lugs. The power wiring connections for this equipment are rated at 90
°
C. See
Table 3‐19 and Table 3‐20 for supplied terminal hardware, Table 3‐21 for
recommended installation parts and tools not supplied by Eaton, and Table 3‐22
through Table 3‐27 for power cable conduit sizes.
Table 3‐20. Supplied External Wiring Terminal Hardware Kit
Part
Size
Quantity
Terminals Used On
Eaton Part Number
Bolt, Grade 5
M12 x 40 mm
30
Ground
180190078-112
Bolt, Grade 5
M12 x 50 mm
86
Rectifier Input, Bypass Input, Battery Input, and
Output
180190078-115
Flat Washer
M12
202
Rectifier Input, Bypass Input, Battery Input,
Output, and Ground
180500036-120
Conical Washer
M12
116
Rectifier Input, Bypass Input, Battery Input,
Output, and Ground
180500037-120
Nut
M12
86
Rectifier Input, Bypass Input, Battery Input,
Output, and Ground
180200001-07
NOTE
Bypass terminations are not applicable to IOM configurations.
Table 3‐21. Recommended Installation Parts and Tools (Not Supplied by Eaton
)
Part
Size
Quantity
Manufacturer
Part Number
Notes
Long Barrel 2‐Hole Lug
2/0 AWG
As required
Thomas & Betts
54862BE
Copper wire only
3/0 AWG
Thomas & Betts
54864BE
4/0 AWG
Thomas & Betts
54866BE
250 MCM
Thomas & Betts
54868BE
300 MCM
Thomas & Betts
54870BE
350 MCM
Thomas & Betts
54872BE
400 MCM
Thomas & Betts
54874BE
500 MCM
Thomas & Betts
54876BE
Manual Hydraulic Crimp Tool
14 Ton
1
Thomas & Betts
TBM14M
Die Set
N/A
1
Thomas & Betts
15506