UPS SYSTEM INSTALLATION
Eaton
Power Xpert 9395P-600 (380V-600V) UPS Installation and Operation Manual
S
P-164000710 Rev 1
www.eaton.com/powerquality
4-6
C
A
U
T
I
O
N
Use care during installation to protect components mounted on the right side of the ISBM section and the
intercabinet wiring harnesses attached to the left side UPM section from damage.
MISE EN GARDE!
Lors de l’installation, prendre soin de protéger les composantes du côté droit du module de contournement
de système intégré (ISBM) et les faisceaux de câbles reliant les armoires du côté gauche du module
d’alimentation universel (UPM).
NOTE
Clearance between the ISBM and the UPM sections must be less than 1/2” so that joining brackets
can be installed.
7.
Using a forklift with the forks in the front forklift slots, position the ISBM section
adjacent to the left side of the previously installed UPM section. Verify that the
ISBM section right side is against the UPM section left side and the front of the
cabinet bases are flush with each other (see Figure 4‐4).
8.
Reinstall the corner channel (see Figure 4‐3) and secure using the retained
hardware.
9.
Reinstall the left middle panel (see Figure 4‐3) and secure using the retained
hardware.
UPM Wireway
(Power wiring harnesses are coiled in this area.)
Tie Wrap Locations
Input Autotransformer T1
Output Autotransformer T2
Figure 4‐4. ISBM and UPM Sections Joined