24
LCD touchscreen display programming
PRC-E Series Instruction Manual
MN014003EN August 2015 www.eaton.com
All circuit breaker buttons on the LCD display should have
a green background with yellow borders after the “Override
OFF” command. If some of the backgrounds are red, see
the “Breaker Button Indications” section of this guide for
further information.
You can visibly verify that all controllable circuit breaker
handles are in the “OFF” position.
otee:
N
The yellow “Override” LED on the PRC controller will
illuminate indicating an override is active.
Clear overrides—panelboard
otee:
N
All of the controllable circuit breakers in all the
selected panelboard will return to their last
commanded normal in-service state which may be
the “ON” or “OFF” position. If there are controllable
circuit breakers that must be left in override for any
reason, an individual controllable circuit breaker clear
override should be done instead of a panelboard clear
override.
Tap “Clear Override” button to clear override for all the
controllable circuit breakers in selected panelboard and
return them to normal in-service state.
otee:
N
The yellow “Override” LED on the PRC-E controller
will turn off.
Overriding all the breakers in ALL
connected panelboards
From “Main Menu” screen, tap the “Breakers” button.
This will display the “Breakers / Select Panelboard” screen.
Override all ON
otee:
N
The “Override All ON” button will override “ON”
all controllable circuit breakers in all panelboards
connected to the controller. If there are controllable
circuit breakers that must be left “OFF” or in-service
for any reason, an individual controllable circuit
breaker override should be done instead of a global
panelboards override.
In the “Breakers / Select Panelboard” screen, tap “Override
All ON” button to override “ON” ALL the controllable circuit
breakers in ALL the panelboards connected to the controller.
This initializes the controllable circuit breaker handles in all
connected panelboards to the “ON” position.
You can visibly verify that all controllable circuit breaker