68
Web page programming
PRC-E Series Instruction Manual
MN014003EN August 2015 www.eaton.com
The digital inputs will have green backgrounds with “OFF”
text when they are open and a red background with “ON”
text when the inputs are closed. In the normal state, there
will be a white filled box beside the status box and yellow
filled if it is overridden.
The universal inputs can be configured as digital (dry-
contact) inputs or analog (voltage level) inputs except on the
PRC750E controller, which has only digital inputs available.
If configured as digital inputs, the “Universal In” will have
green backgrounds with “OFF” text when they are open
and a red background with “ON” text when the inputs are
closed. In the normal state, there will be a white filled box
beside the status box and yellow filled if it is overridden.
If configured as analog inputs, the “Analog In” displays the
percentage of the full scale voltage applied to the input.
The background color is green in the normal status. In the
normal state, there will be a white filled box beside the
status box and yellow filled if it is overridden.
The “Analog Out” displays the percentage level of the
analog output. In the normal state, there will be a white
filled box beside the status box and yellow filled if it is
overridden.
Controls
Controls are logical statements that utilize the inputs to
control the groups.
otee:
N
From the Web page, a control can be created to
command a group only. If another type of point
control is needed, PRC Lighting Optimization
software (PRCLOS) will be required.
To create a control, click the “Controls” tab.
This opens the “Control” list.
Listed are controls created to command internal points,
i.e., circuit breakers, groups, outputs, etc.
Control configuration
The “Type” refers to the input type.
Type options:
●
●
Maintained change
●
●
Reverses group status on input state change
●
●
Maintained normally open
●
●
Group action commanded on input closure and
reversed when open
●
●
Maintained normally closed
●
●
Group action commanded when input is open and
reversed when closed
●
●
Momentary three-wire
●
●
Two inputs are used, one for the ON command and the
other for the OFF command
●
●
Momentary On/Off
●
●
After a momentary closure of input, the state of the
output will be reversed
●
●
Motion sensor
The “Switch(es)” refers to the input or inputs used to
control the action.
Switch options:
●
●
DI 1–8
●
●
UI 1–8
The “Group” is the commanded group and the action to
be taken. When using the Web page the only available
action is “On”.
Group options:
●
●
GRPA ON, GRPB ON,…GRPP ON