72
Web page programming
PRC-E Series Instruction Manual
MN014003EN August 2015 www.eaton.com
Input the selected circuit breaker address using the keyboard.
otee:
N
The circuit breaker address must be written in
the “Panel”:”Breaker#””B” format, which is
“1:1B”-“8:42B” (example- Panel 1/Breaker 17 would
be written as 1:17B or Panel 2 (expansion panelboard
connected to controller)/breaker 3, would be written
as 2:3B.
Next, a button press action must be assigned to the button.
Setting the digital point action
Click the “Action” dropdown arrow next to the button to be
programmed.
This opens the dropdown list for a quick pick of the actions
available.
Click to select the required action.
The actions are:
None
: No digital point action upon button press, however,
the analog point can still be set.
Off
: The digital point is commanded Off when the button is
pressed, if its current status is Off, there will be no change.
On
: The digital point is commanded On when the button is
pressed, if its current status is On, there will be no change.
Toggle
: The digital points current state will be reversed. If
at the button press the point is On, it will be commanded
Off, and if at the button press the point is Off, it will be
commanded On.
Setting the button analog point control
The analog point settings can control the analog output
of the switch, the calculated points (“C” points) of the
controller or the analog outputs of the controller. The digital
switch analog output control is listed as “LIGHT_LVL”. This
setting is a numeric value representing the percentage of
the 0–10 V output or setpoint for the light level. For more
information on the setpoint, see the “Digital Switch Sensor”
section of this guide.
The “C” points, 1C–32C, are values that can be passed to
the PRC-E controller. These points are numeric values that
can be used in calculations and other complex logic controls
in the controller. The PRC-E controller analog output, 1O–8O,
can also be set directly from the switch. This setting is a
numeric value representing the percentage of the 0–10 V
output.
The analog point values can be “set to”, “incremented by”,
or “decremented by” the amount entered in the “Value”
input box.
Editing the analog points
Click the “Analog Point” dropdown arrow of the button to
be programmed.
This opens the dropdown list for a quick pick of the
“LIGHT_LVL” or “C” points.
Click to select the required analog point.
To choose an analog output in the controller, click the
“Analog Point” textbox of the button to be programmed.
This opens the textbox for edit.
Input the selected analog point address using the keyboard.