34008030EN/AD - Page 34
8. Appendices
8.1 Technical specifications
(1) If the output voltage is 200V - 250V, the output power is 4500VA / 4000W.
(2) With one
EXB
module or more, the standard output power is 5000VA / 4000W.
(3) Values for 70% / 100% of UPS output.
(4) Programmable: 200V / 208V / 220V /
230V
/ 240V / 250V using the
UPS Config
software.
(5) Frequency-converter mode is programmable using the
UPS Config
software.
MX 4000
MX 5000
MX EXB
Output power
4000 VA /
3600 W
5000 VA
(1)
/
4500 W
(2)
Electrical supply network
◗
Rated input voltage
◗
Input voltage range
◗
Frequency
◗
Power factor
◗
Leakage current
Single phase 230 V
120 / 156 V to 280 V
(3)
50/60 Hz (autoselection)
> 0.99
7 mA max.
Load output
◗
Voltage
◗
Frequency
◗
Harmonic distortion
◗
Overload capacity
Single phase 230 V ±3%
(4)
50/60 Hz ±0,5%
(5)
< 3%
105% continuous, 110% 2min,
125% 1min, > 150% 0.5s
Battery
15 x 12V - 5 Ah,
sealed lead acid,
maintenance free
15 x 12V - 5 Ah,
sealed lead acid,
maintenance free
Two 15 x 12 V - 5 Ah
strings, sealed lead acid,
maintenance free
Environment
◗
Operating temperature range
◗
Relative humidity
◗
Storage temperature range
◗
Altitude
◗
Noise level
0°C to 40°C
20% to 90% (non-condensing)
-25°C to 40°C
0 to 1000 m without derating
< 45 dBA