MAINTENANCE
1.
Perform visual, electrical, and mechanical inspections
on a regular basis. The environment and frequency
of use should determine this. However, it is
recommended that checks be made at least once
a year. We recommend an Electrical Preventive
Maintenance Program as described in the National
Fire Protection Association Bulletin NFPA No. 70B:
Recommended Practice For Electrical Equipment
Maintenance
(www.nfpa.org).
2.
The lens should be cleaned periodically to ensure
continued lighting performance. To clean, wipe the
lens with a clean, damp cloth. If this is not sufficient,
use a mild soap or a liquid cleaner such as Collinite
NCF or Duco #7. Do not use an abrasive, strong
alkaline, or acid cleaner. Damage may result.
3.
Visually check for undue heating evidenced by
discoloration of wires or other components, damaged
parts, or leakage evidenced by water or corrosion
in the interior. Replace all worn, damaged, or
malfunctioning components, and clean gasket seals
before putting the luminaire back into service.
4.
Electrically check to make sure that all connections
are clean and tight.
5.
Mechanically check that all parts are properly
assembled.
REPLACEMENT PARTS
Crouse-Hinds PVM Series Champ Luminaires are designed
to provide years of reliable lighting performance. However,
should the need for replacement parts arise, they are
available through your authorized Crouse-Hinds distributor.
Assistance may also be obtained through your local
Crouse-Hinds representative.
Crouse-Hinds Sales Service Department, 1201 Wolf Street,
Syracuse, New York 13208, Phone (866) 764-5454.
IF 1628 • 05/22
Copyright © 2022, Eaton’s Crouse-Hinds Division
Page 3
FIELD ASSEMBLED FIXTURES
PVM Series Lighting Fixtures, 50-140 Watt
Complete lighting fixture consists of cover, LED luminaire
PVM9L/7L/5L
DM1, DM2, DM3, DM4
CEILING
CM3 1 IN.
CM2 3/4 IN.
PENDANT
HPM2 3/4 IN.
APM2 3/4 IN.
APM3 1 IN.
WALL
TWM2 3/4 IN.
TWM3 1 IN.
STANCHION
1 1/2 IN
JM5
PM5
1 1/2 IN.
NPT
Entries
1
5
5
1
1
PVM3L/11L
All statements, technical information and recommendations contained herein are based on information and
tests we believe to be reliable. The accuracy or completeness thereof are not guaranteed. In accordance with
Crouse-Hinds “Terms and Conditions of Sale,” and since conditions of use are outside our control, the purchaser
should determine the suitability of the product for his intended use and assumes all risk and liability whatsoever in
connection therewith.
Eaton’s Crouse-Hinds Division
IF 1628
1201 Wolf Street, Syracuse, New York 13208 • USA
Revision 2
Copyright © 2022
Revised 05/22
Supersedes 11/11
LED MODULE REPLACEMENT
INSTRUCTIONS
1.
Turn off electrical power to the luminaire before
opening.
2.
Loosen captive closing screw, open luminaire, and
leave hanging on cover module hinge hook.
3.
Disconnect supply wire from luminaire wire leads
and remove luminaire from cover module.
4.
At workbench, remove wire nut connections from
both LED drivers’ DC outputs to LED module (see
Step 1).
5.
Unthread the three housing bolts using a 3/16” hex
tool; do not remove bolts from assembly.
6.
Carefully separate the heat sink/driver housing from
the LED module, pulling the LED wires through the
bushing in the driver housing.
7.
Remove any gasket material from the bottom of the
heat sink with a shop rag (see Step 2).
8.
Place new LED module on workbench and inspect
gasket to ensure proper sealing during assembly
(see Step 3).
9.
Gently place heat sink/driver housing into LED
module while feeding the paired wires from the LED
module through the bushing in the driver housing,
being sure to align the bolts with the tapped holes in
the LED module.
10. Thread the three (3) housing bolts into the LED
module using a 3/16” hex tool. Torque bolts to 50
in.-lbs. (5.7 N-m).
11. Use supplied wire nuts to connect LED driver DC
output to LED module wires, noting correct polarity.
12. Mount and wire luminaire per Installation
Instructions.
STEP 1
STEP 2
STEP 3