Internal Battery Instructions for the Eaton 9355 UPS (20/30 kVA)
164201708—Rev 03
9
CAUTION
Caution should be taken when connecting the battery terminals. Potential Lethal voltages are present.
8.
Connect the positive (+) connector (short red wire) of the battery tray wire harness (see
) to the
positive battery terminal at the front of the tray, then run the rest of the wire to the back of the tray for later
use. (see
for more detail)
Figure 6. Battery Tray Wire Harness
Red Wire
Black Wire
9.
Connect the long black wire of the battery tray harness to the negative battery terminal at the back of the
tray.
10. Tie wrap the wires to the jumper wires in three places using the supplied tie wraps.