Eaton PXGMS Card Quick Start Instructions P-164000208—Rev 2
3
Section 2
Install the Card
Note:
The hot-swappable PXGMS card can be installed without turning off the
UPS or disconnecting the load.
Note:
If your UPS is a 93PM, there may be a metal strip that prevents you
from installing the PXGMS card. If so, locate the metal strip bolted to
the top of the UPS. Remove the three bolts that attach the metal strip.
Then, follow the procedure to install the PXGMS card.
To install the PXGMS card:
1.
On the PXGMS card, verify that all six DIP switches are in the OFF position
(see Figure 1).
Figure 1. Verify DIP Switches are OFF
2.
If not already done, record the MAC address from either the shipping box
label or the label on this card for future reference (see the "Installation
Checklist" on page 2).
3.
Remove the minislot cover from the UPS. Retain the screws.
Note:
If another card is already installed with an attached communication
cable, disconnect the cable and then remove the card.
4.
To prevent electrostatic discharge (ESD), place one hand on a metal surface,
such as the UPS rear panel.
Ident
Power
Act
100
PXGMS UPS
Restart
TX
RX
Setup
CMN
Status
DHCP
EMP
Ethernet 10/100
+
-
2
1
3 4
5 6
ON
OFF