Profibus DP-VO diagnostics
Until the PCAM is parameterized and configured by the Profibus
master, a request for diagnostics by the master will result in the
PCAM returning only the mandatory 6-byte Profibus diagnostics
information. Once successfully parameterized and configured, the
PCAM will append additional device-related diagnostics information
to the mandatory Profibus diagnostics, as described by
Table 10
.
Table 10. DP-VO unit diagnostics definitions
byte
bits
Value
Description
7
08H
Header: device-related
diagnostics, length = 8 bytes
8
7.0
81H
Type: status message
9
15..8
Slot
10
23..16
00H
Specifier
11
24
1
No communications with trip unit
25
1
Data object 1 invalid
26
1
Data object 2 invalid
27
1
Data object 3 invalid
28
1
Data object 4 invalid
29
1
Data object 5 invalid
30
1
Data object 6 invalid
31
1
Data object 7 invalid
12
32
1
Data object 8 invalid
33
1
Data object 9 invalid
34
1
Data object 10 invalid
35
1
Data object 11 invalid
36
1
Data object 12 invalid
37
1
Data object 13 invalid
38
1
Data object 14 invalid
39
1
Remote open/closed not enabled
13
40
1
EEPROM error alarm
41
1
RAM error alarm
42
1
Setpoints error alarm
43
1
Watchdog alarm
44
1
Check aux. switch alarm
45
1
Breaker mechanism fault
46
1
Breaker shunt trip problem
47
1
Operations count alarm
14
48
1
Earth fault alarm
49
1
Low power factor alarm
50
1
Total harmonic distortion alarm
51
1
Frequency out of bounds alarm
52
1
Historic trip occured
53
1
Breaker in maintenance mode