Intelligent Technologies (
IT.
) QSNAP
12
Pub. No. MN05001001E
February 2002
Table 11: Default Input Data
Output Data
Use
Tables 12
and
13
when setting up the QSNAP output data.
Table 12: Default Output Data
Table 13: Output Assembly Data Definitions
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
3-Phase Average RMS Current LSB
Byte 0
3-Phase Average RMS Current
Byte 1
3-Phase Average RMS Current
Byte 2
3-Phase Average RMS Current MSB
Byte 3
% Thermal Capacity LSB
Byte 4
% Thermal Capacity MSB
Byte 5
Fault/Warning Codes LSB
Byte 6
Fault/Warning Codes MSB
Byte 7
Reserved Warning
Faulted
Local
Control
Resetting Permissive Running 2 Running 1
Byte 8
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Reserved
Reserved
Local
Control
Local /
Remote
Fault
Reset
Permissive Run 2
Run 1
Byte 8
Data
Description
Run 1
Energize the first starter when Permissive is 1
Run 2
Energize the second starter when Permissive is 1
Fault Reset
Reset the fault
Permissive
Starter Permissive, O – Stops the starter, I – Enables to run the starter