UL
®
Cautions, Warnings and Instructions
UL
®
File: E253552
UL61800-5-1
CSA C22.2 No 274
USA: ULus
Indicates Investigated to United States Standard UL61800-5-1 - Listed.
Canada: cUL
Indicates Investigated to Canadian Standard CSA 22.2 No.274 - Listed
Electrical ratings
General
– These devices are solid state variable/speed ac drive inverters which
convert a fixed frequency three phase input voltage to a 3-phase, variable
frequency, variable voltage output. The inverter automatically maintains the
required volts-Hz ratio allowing the ac motor to run at its optimum efficiency
and provide constant torque capability through the motor speed range.
– The power conversion equipment provides solid state motor overload protection.
– Over-Current function was evaluated. Maximum current limit is 150 percent
of FLC. The adjustable range is 0 to 150 percent of FLC.
– Drive is provided with solid state short circuit protection circuitry which is
the same throughout the series. Current sensing is accomplished by
monitoring the DC bus and/or all the motor outputs.
– These drives or control units have not been evaluated as providing a safety
or limiting feature.
– The devices use the supplied thermocouple in the IGBT packs to control
thermal functions – 100 % production test used to confirm functionality.
– These devices are for installation in overvoltage category III and
pollution degree 3.
– Auxiliary control outputs intended to drive resistive load.
Short circuit rating
RASP5-…-xxxR (disconnect switch)
Environmental ratings
– Maximum ambient air temperature: 55 °C
– Enclosure type 12
Further specifications and information
– Use copper conductors only
– 75 °C wire only
– Integral solid state short circuit protection does not provide branch circuit
protection. Branch circuit protection must be provided in accordance with
the National Electrical Code and any additional local codes or the equivalent.
Model – 400 V Range
Input
Output
(3-phase)
(3-phase)
Frame Size
Model number
FLA
FLA
Power
kW
Power
HP
1A
RASP5-2…
2.4
2.4
0.75
1.0
1A
RASP5-3…
3.3
3.3
1.1
1.5
1A
RASP5-4…
4.3
4.3
1.5
2.0
1A
RASP5-5…
5.6
5.6
2.2
3.0
1B
RASP5-6…
6.8
6.8
3.0
4.0
1B
RASP5-8…
8.5
8.5
4.0
5.0
Frame size 1A = no external fan fitted.
Frame size 1B = external fan fitted.
Input voltage 380 - 480/277 V AC, 50/60 Hz
Output voltage 20 - 500 V AC, 0 - 500 Hz
Terminals –
All Models
Qty
Maximum ratings
Sensor supply
3
24 V 100 mA
Motor Brake
1
600 mA 400 V
(6 A < 120 ms)
Model
Short circuit rating (kA)
Fuses
(J-Type)
Breakers
(Type C)
…When protected by
100 kA
… Class J fuses
RASP5
10 kA
… Circuit breaker (Type C)
65 kA
… Type E Combination Motor Controller
… Class J fuses
RASP5-…-xxxR
(with repair switch)
10 kA
… Circuit breaker (Type C)
… Type E Combination Motor Controller
NOTICE
Suitable for use on a circuit capable of delivering not more than 100 000 rms
symmetrical amperes, 480 volts maximum. Suitable for motor group
installation. When protected by J class fuses rated 30 A.
Suitable for use on a circuit capable of delivering not more than 65 000 rms
symmetrical amperes, 480 volts maximum. When protected by type E
combination motor controller model PKZM4-32 manufactured by Eaton
rated 480Y/277 V AC 20 HP.
Suitable for use on a circuit capable of delivering not more than 10 000 rms
symmetrical amperes, 480 volts maximum. Suitable for motor group
installation. When protected by a circuit breaker having an interrupting rating
not less than 10 000 rms symmetrical amperes, 480 volts maximum, rated 32 A.
NOTICE
Suitable for use on a circuit capable of delivering not more than 10 000 rms
symmetrical amperes, 480 volts maximum. Suitable for motor group
installation. When Protected by J Class fuses rated 30 A.
Suitable for use on a circuit capable of delivering not more than 10 000 rms
symmetrical amperes, 480 volts maximum. Suitable for motor group
installation. When protected by circuit breaker having an interrupting rating
not less than 10 000 rms symmetrical amperes, 480 volts maximum, rated 32 A.
Suitable for use on a circuit capable of delivering not more than 10 000 rms
symmetrical amperes, 480 volts maximum. When protected by type E
combination motor controller model PKZM4-32 manufactured by Eaton
rated 480Y/277 V AC 20 HP.
WARNING
The opening of the branch-circuit protective device may be an
indication that a fault has been interrupted. To reduce the risk of fire
or electric shock, current-carrying parts and other components of the
controller should be examined and replaced if damaged.
ATTENTION
THE OPENING OF THE BRANCH-CIRCUIT PROTECTIVE DEVICE
MAY BE AN INDICATION THAT A FAULT HAS BEEN INTERRUPTED.
TO REDUCE THE RISK OF FIRE OR ELECTRIC SHOCK, CURRENT-
CARRYING PARTS AND OTHER COMPONENTS OF THE CONTROLLER
SHOULD BE EXAMINED AND REPLACED IF DAMAGED. IF BURNOUT
OF THE CURRENT ELEMENT OF AN OVERLOAD RELAY OCCURS,
THE COMPLETE OVERLOAD RELAY MUST BE REPLACED.