Eaton Remote Power Panel (RPP) User’s Guide 164202125—Rev 5
www.eaton.com/powerquality
29
Chapter 4
Operation
This chapter describes how to use the Eaton Remote Power Panel (RPP), including front panel operation, initial
configuration, and startup and shutdown.
Control Panel Functions
The RPP with the Energy Management System (EMS) option has a five-button graphical LCD with backlight
(see Figure 16). Depending on the level of meter installed, the display provides useful information about the
RPP itself, events, measurements, and settings.
Figure 16. EMS Meter Display
The following table shows the indicator status and description.
Indicator
Status
Description
ON
Green
On
The RPP is operating normally.
Off
The RPP is turned off and will not turn on automatically.
O/L
Yellow
On
One or more phase is in overload; or there is an alarm or warning for neutral
overload, ground overload, main panel breaker overload, or panel breaker
overload; or there is a transformer overload.
OFF
Yellow
On
The EMS-RPP is de-energized or output voltage is less than 25% of nominal.
AL
Red
Flashing
There is a new RPP alarm condition. See “Troubleshooting” on page 45 for
additional information.
To acknowledge the alarm and silence the horn, press any button.
On
An acknowledged alarm condition exists.
PRESS ANY KEY TO CONTINUE
Power On Indicator (green)
Overload Indicator (yellow)
Alarm Indicator (red)
Control Buttons for the LCD Menu Options