background image

RVU 12-24kV VACUUM CIRCUIT BREAKER 

DEFINITION

RVU  Series  12-24kV  Vacuum  Circuit  Breaker  is  a  three-phase  AC  indoor  breaker  with  12-24kV  rated  voltage  suitable  for 

air  insulated  switchgear  and  can  be  applied  in  controlling  and  protecting  electrical  equipment  in  industrial  and  mineral 

enterprises, power plants and substations. Operation mechanism is installed laterally. 

The product conforms to the IEC 62271-100 standard. Short circuit type tests are performed in KEMA High Power Laboratory 

in the Netherlands. RVU series provide safe and reliable performance. The embedded poles of RVU have the technique of 

ventilation and convection. Besides the vacuum interrupter has low resistance and high number of short circuit breaking. 

AII of that reduce the power consumption and the temperature rising due to the longtime running of circuit breaker. 

Under  normal  conditions  the  interrupter  is  in  closed  position. 
Arcing  is  occured  within  the  interrupter  by  withdrawing  the 
moving  contact  from  stationary  contact.  This  arc  burns  in  the 
metal  vapor  evaporated  from  local  hot  spots  on  the  contact 
surfaces.  The  metal  vapour  continually  leaves  the  inter-contact 
region and recondenses on the contact surfaces and surrounding 
metal  vapor  condensation  shield.  The  latter  is  usually  isolated 
from  both  contacts  and  serves  to  protect  the  glass  or  ceramic 
envelope from vapor deposition. At current zero, vapor production 
ceases and the original vacuum condition is rapidly approached. 
The dielectric strength of the interrupter also increases, and the 
circuit is interrupted.

2

Summary of Contents for RVU 12 RVU 24

Page 1: ...RVU SERIES 12 24kV EMBEDDED POLE VACUUM CIRCUIT BREAKER www ulusoyelektrik com tr...

Page 2: ...mers manage electrical hydraulic and mechanical power more reliably efficiently safely and sustainably We provide integrated solutions that help make energy in all its forms more practical and accessi...

Page 3: ...ain Components Technical Characteristics Drawing Dimensions Circuit Breaker Secondary Wiring Diagram Manuel Operating Instructions Warning and Recommendations Circuit Breaker Storage and Packaging Dim...

Page 4: ...istance and high number of short circuit breaking AII of that reduce the power consumption and the temperature rising due to the longtime running of circuit breaker Under normal conditions the interru...

Page 5: ...um Poles Motion Transfer Cam Mechanism Compartment Wheels Connector Plug Absorber 8 9 10 11 13 12 14 Mechanical Interlock Counter Closing Push Button Opening Push Button Spring Charge Discharge Signal...

Page 6: ...RVU 12 24kV VACUUM CIRCUIT BREAKER 1 Spring Charge Motor 4 Auxiliary Contacts 2 Opening Coil 5 Anti Pumping Relay 3 Closing Coil 6 SpringChargingSwitch 7 Charging Gear 8 Counter 9 MechanicalInterlock...

Page 7: ...USER MANUAL SERVICE INSTRUCTIONS 12 Closing Spring 11 Opening Spring 10 Mechanical Operation Lever Hole...

Page 8: ...t Isc 25kA Rated Short Time Withstand Current 3 sec Operating Sequence O 300msec CO 3min CO Interrupter Vacuum DC Component Max 40 Cable Charging Breaking Current 31 5A System Neutral Neutral earth or...

Page 9: ...USER MANUAL SERVICE INSTRUCTIONS Drawings Dimensions Dimensions are given in mm...

Page 10: ...RVU 12 24kV VACUUM CIRCUIT BREAKER CIRCUITBREAKERSECONDARYWIRINGDIAGRAM VACUUM EMBEDDED CIRCUIT BREAKER CONNECTION DIAGRAM...

Page 11: ...en In order to close the circuit breaker push the red closing button The circuit breaker position indicator will turn into I closed position After the closing operation spring charged discharged signa...

Page 12: ...ts dismounted Inside of coils should be dismounted pull outward Put the new coil inside and screw the bolts Control the coil by your hand if it works or not then make the electrical connections Dismou...

Page 13: ...ng relay to insert its place Insert the link Pull down the track clip to take off motor protection fuse Push the locks of the clip and remove the connections of electrical cables Remove bolts After re...

Page 14: ...avoid any hitting Never clean the poles by using the materials which have unsuitable insulation levels Contact surfaces needs to be clean before making bar connections with a oil free solvent or aceto...

Page 15: ...tely opening after closing Mechanism Mechanism might not be charged please check it Any opening component The failure might continue because of high voltage Relay settings must be wrong please check i...

Page 16: ...edia to get the latest product and support information www ulusoyelektrik com tr www eaton com 2020 Eaton All Rights Reserved May 2020 Eaton is a registered trademark All trademarks are property of th...