RVU SERIES 12-24kV
EMBEDDED POLE
VACUUM CIRCUIT BREAKER
www.
ulusoyelektrik
.com.tr
Page 1: ...RVU SERIES 12 24kV EMBEDDED POLE VACUUM CIRCUIT BREAKER www ulusoyelektrik com tr...
Page 2: ...mers manage electrical hydraulic and mechanical power more reliably efficiently safely and sustainably We provide integrated solutions that help make energy in all its forms more practical and accessi...
Page 3: ...ain Components Technical Characteristics Drawing Dimensions Circuit Breaker Secondary Wiring Diagram Manuel Operating Instructions Warning and Recommendations Circuit Breaker Storage and Packaging Dim...
Page 4: ...istance and high number of short circuit breaking AII of that reduce the power consumption and the temperature rising due to the longtime running of circuit breaker Under normal conditions the interru...
Page 5: ...um Poles Motion Transfer Cam Mechanism Compartment Wheels Connector Plug Absorber 8 9 10 11 13 12 14 Mechanical Interlock Counter Closing Push Button Opening Push Button Spring Charge Discharge Signal...
Page 6: ...RVU 12 24kV VACUUM CIRCUIT BREAKER 1 Spring Charge Motor 4 Auxiliary Contacts 2 Opening Coil 5 Anti Pumping Relay 3 Closing Coil 6 SpringChargingSwitch 7 Charging Gear 8 Counter 9 MechanicalInterlock...
Page 7: ...USER MANUAL SERVICE INSTRUCTIONS 12 Closing Spring 11 Opening Spring 10 Mechanical Operation Lever Hole...
Page 8: ...t Isc 25kA Rated Short Time Withstand Current 3 sec Operating Sequence O 300msec CO 3min CO Interrupter Vacuum DC Component Max 40 Cable Charging Breaking Current 31 5A System Neutral Neutral earth or...
Page 9: ...USER MANUAL SERVICE INSTRUCTIONS Drawings Dimensions Dimensions are given in mm...
Page 10: ...RVU 12 24kV VACUUM CIRCUIT BREAKER CIRCUITBREAKERSECONDARYWIRINGDIAGRAM VACUUM EMBEDDED CIRCUIT BREAKER CONNECTION DIAGRAM...
Page 11: ...en In order to close the circuit breaker push the red closing button The circuit breaker position indicator will turn into I closed position After the closing operation spring charged discharged signa...
Page 12: ...ts dismounted Inside of coils should be dismounted pull outward Put the new coil inside and screw the bolts Control the coil by your hand if it works or not then make the electrical connections Dismou...
Page 13: ...ng relay to insert its place Insert the link Pull down the track clip to take off motor protection fuse Push the locks of the clip and remove the connections of electrical cables Remove bolts After re...
Page 14: ...avoid any hitting Never clean the poles by using the materials which have unsuitable insulation levels Contact surfaces needs to be clean before making bar connections with a oil free solvent or aceto...
Page 15: ...tely opening after closing Mechanism Mechanism might not be charged please check it Any opening component The failure might continue because of high voltage Relay settings must be wrong please check i...
Page 16: ...edia to get the latest product and support information www ulusoyelektrik com tr www eaton com 2020 Eaton All Rights Reserved May 2020 Eaton is a registered trademark All trademarks are property of th...