29
Instructional Leaflet
IB2C12063H03
Effective March 2012
Instructions for Installation, Operation and
Maintenance of Magnum SB Insulated Case
Low Voltage Power Circuit Breakers
EATON CORPORATION
www.eaton.com
Drawout type circuit breakers: Compatible secondary plug-
in connectors are mounted on the top front portion of the
drawout cassette (
Figure 40
) . These connectors match and plug
into the circuit breaker mounted connectors . Contact points
are wired from the cassette’s plug-in connectors to cassette
mounted terminal blocks . The terminal blocks are also mounted
on the top front portion of the cassette . The secondary
terminals have finger-proof hinged covers with small holes for
probe testing .
Fixed type circuit breakers: There are two secondary
connection options:
(1) Without Terminal Block
(2) With Terminal Block
1 Without Terminal Block - If a terminal block for customer
use is not required, the circuit breaker is supplied with
both plug-in connectors (male and female) just described
in the two previous paragraphs . The plug-in connectors are
joined and attached to the top portion of the circuit breaker .
The customer can plug secondary wiring with crimpon
connectors into back of the plug-in connectors; subsequently
the connections to the circuit breaker can be quickly joined or
separated as required .
2 With Terminal Block - For those customers preferring to
wire to a terminal block, terminal blocks with finger-proof
hinged covers are added to the secondary configuration
just described for a fixed circuit breaker “without a
terminal block .” The terminal blocks are wired to the plug-in
connectors and also permanently attached to the upper rear
portion of the circuit breaker (
Figures 18 and 19
) .
A standard tool is available from the plug-in connector
manufacturer (AMP) to facilitate the removal of secondary
wiring from a plug-in connector, or contact Cutler-Hammer
for assistance (
Figure 41
) . The connector halves must be
separated to use this tool .
Connection Diagrams
The connection diagrams for all Magnum SB circuit breakers
using Digitrip RMS trip units are shown in
Figures 42
through
59
.
Closed Hinged Covers
with Testing Holes
Terminal Blocks
Figure 40. Typical Cassette Mounted Secondary Wiring
Figure 41. AMP Secondary Wiring Removal Tool