If the SC100 is to report alarms to PowerManagerII then click on
+
to expand
PowerManager Callback
. Configure the following settings:
Alarm Report:
Select the type of event(s) that will initiate the dial-out
process.
Report Maximum Retries:
Set to the number of times the SC100 is to try to connect
with a remote modem, if the first attempt fails.
After this number of retries the SC100 will try the next
number in the Dial Out Numbers table.
Dialing will stop if none of the numbers in the Dial
Out Number Table connect.
Report Retry Interval:
Set to the required interval between retries.
Dial Out Number(s):
Type the telephone number(s) to be called.
Consult the modem documentation for appropriate
dial modifiers.
DCTools or PowerManagerII Communications Setup
► To connect to the SC100 with DCTools or PowerManagerII:
1
If not already installed, install the PC modem (hardware and software) according to the
manufacturer's instructions.
2
Install
DCTools/PowerManagerII
on the PC/laptop.
3
Double-click the
DCTools/PowerManagerII
icon to open the
Connection Manager
window.
4
Go to
Connection
>
New
to open a new connection dialog box.
5
Enter:
Connection Name: <as required>
Comms Enabled:
True
Protocol:
S3P
Connect Using:
Select the COM port used by the modem (if external) or the
modem name.
S3P Address:
0
(
0 = Broadcast, 1-65279 = individual address
)
Phone Number:
The number of the PSTN line used by the modem.
Modem Logon:
Clear if a logon script is not required for the modem.
Select if a logon script is required. Click
Logon Script
to define.
For more details, see DCTools/PowerManagerII online help
(press F1).