SC300 Handbook
106
Copyright © 2007-2018 Eaton Corporation. All Rights Reserved.
IPN 997-00012-03 B2 Issue B2 July 2018
PowerManagerII Communications Setup (if required)
► To connect to the SC300 with PowerManagerII:
1
Install PowerManagerII on the PC/laptop.
2
Double-click the PowerManagerII icon to open the connection manager.
3
Go to
Connection
>
New
to open a new connection dialog box.
4
Enter:
Connection Name: <as required>
Comms Enabled:
True
Protocol:
S3P
Connect Using:
Ethernet
S3P Address:
0
(
0 = Broadcast, 1-65279 = individual address
)
Server IP Address: Allocated by network administrator
Server Port:
Allocated by network administrator
Telnet
Cleared
5
Press OK. PowerManagerII will now connect to the SC300.
6
If required, access to the SC300 via PowerManagerII can be password controlled. See Write
Access Password on page 116.
Communication via Web Browser
The SC300 system controller has an in-built web server. This allows a PC/laptop with a
standard web browser to control and monitor the SC300 via an IP network.
► To connect to the SC300 with web browser:
1
Set up Ethernet communications and connect the SC300 to the IP network. See Ethernet
Communications on page 104.
2
Open a web browser window.
Recommended web browsers: Microsoft Internet Explorer 10 or later, Mozilla Firefox 3.0 or
later, Chrome V63 or later.
Internet Explorer 10/11: Ensure that Compatibility Mode is turned off. Go to Tools >
Compatibility View Settings.
3
Type the IP Address of the SC300 into the address bar of the browser.
The SC300 web communications is set by default to http disabled and https enabled. If necessary,
type "https://" before the IP Address.
4
If https is being used, and this is the first connection to that SC300, the browser will ask
whether you to “confirm a security exception”, or similar. You will need to add an exception,
accept the certificate. and then continue,. The exact details will depend on the browser.
5
The SC300 web server
Log On
page will appear.
6
If required, type a Logon ID and Password. Otherwise select
Default User
.