System Operation
Copyright © 2007-2018 Eaton Corporation. All Rights Reserved.
IPN 997-00012-03 B2 Issue B2 July 2018
37
PLR may be triggered manually from the SC300 web interface, automatically from a Smart Alarm,
or remotely from EDREM or a similar application.
► To enable PLR
•
Use the SC300 keypad to go to:
Control Processes > Peak Load Reduction
.
•
Or, in DCTools/Web go to:
Control Processes >
Peak Load Reduction
•
Set
Enable
to
Enabled.
•
Set
Maximum Duration
and
Low Voltage Limit
as required.
► To manually trigger PLR
•
Use the SC300 keypad to go to:
Control Processes > Peak Load Reduction
.
•
Or, in DCTools/Web go to:
Control Processes >
Peak Load Reduction
•
Set
Scheduled Start Time
and
Scheduled Duration
as required.
► To use a Smart Alarm to activate Peak Load Reduction (optional)
•
In DCTools/Web go to:
Alarms >
Smart Alarms
•
Configure
a
Smart Alarm with the appropriate trigger conditions for PLR. Note the Smart
Alarm number.
•
Go to:
Control Processes >
Peak Load Reduction
•
Set
Activating Smart Alarm
to the appropriate Smart Alarm number.