The following information is available about Load Based Rectifier Shutdown.
Parameter
Description
Where to find:
Load Based Run
Time
The run time of each rectifier
DCTools/Web: Rectifiers
Solar Power
The total power produced by solar chargers
DCTools/Web: Rectifiers >
Load Based Rectifier
Shutdown
System Power
The percentage of maximum output power that
the system is providing. This is used by LBRS to
calculate whether to shut down or start up
rectifiers
DCTools/Web: Rectifiers >
Load Based Rectifier
Shutdown
Configuration
The following parameters must be configured to set Load Based Rectifier Shutdown.
Parameter
Description
Where to find:
Shutdown
Set to Automatic to enable LBRS
SC300: Rectifiers >
Configuration
DCTools/Web: Rectifiers >
Configuration
Redundancy
The number of spare rectifiers kept running:
N Plus 2: Two spare rectifiers are always
running. Three or more rectifiers are always
running.
N Plus 1: One spare rectifier is always running.
Two or more rectifiers are always running.
N: If an alternative energy source is powering
the load, then all rectifiers can be shut down.
Otherwise at least one rectifier is always
running. There is no redundant rectifier.
SC300: Rectifiers > Settings
(tab) > LBRS
DCTools/Web: Rectifiers >
Load Based Rectifier
Shutdown
High Threshold
LBRS restarts one or more rectifiers if the load is
more than this percentage of the total rectifier
capacity. Typical: 60%.
Low Threshold
LBRS shuts down one or more rectifiers if the
load is less than this percentage of the total
rectifier capacity. Typical: 40%.
Shutdown does not occur if shutting down a
rectifier would push load percentage above
High
Threshold.
Interval
The time interval that the SC300 will cycle
rectifiers when the LBRS process is active.
Reset Run Times
Sets the run time of all rectifiers to zero.