System Operation
Copyright © 2007-2018 Eaton Corporation. All Rights Reserved.
IPN 997-00012-03 B2 Issue B2 July 2018
91
► To set the DO Control Timeout Period
•
On DCTools/web, go to
Digital Outputs
:
•
Set DO Control Timeout Period to the required value. This sets the maximum
time that a digital output will remain in manual control. After that time it reverts
to automatic control.
► To manually control a digital output
Either:
•
On DCTools/web, go to
Digital Outputs
:
•
Expand the
Digital Outputs
table.
•
In the
Control State
column of the required digital output, select
Active
or
Inactive
.
•
Or, use the SC300 keypad to go to
Digital Outputs
:
•
Select the required digital output. Press
Edit
.
•
Select
Active
or
Inactive
. Press
Save
.
•
The
DO Manual
alarm (if enabled) will activate.
•
The corresponding digital output will Energize or De-Energize, as selected in the
Active State
column of the
Digital Outputs
table.
The digital output will revert to Automatic after the DO Control Timeout Period.
While
Active
or
Inactive is selected, t
he DO will not be operated by any active alarms mapped to
it. Set Control State back to Automatic to allow mapped alarms to operate the digital output.
► To set the state of a digital output from PowerManagerII
•
In
Web
, set the
Group
of one or more digital outputs to a non-zero value.
Only digital outputs with a non-zero Group are visible in PowerManagerII
•
In
PowerManagerII
select the SiteManager group item.
•
Click on the
Realtime
tab.
•
From the drop down list beside the digital output select
Active Manual
or
Inactive Manual
.
•
The
DO Manual
alarm (if enabled) will activate.
•
The corresponding digital output will Energize or De-Energize, according to its
Active State.
While
Active Manual
or
Inactive Manual is selected, t
he DO will not be operated by any active
alarms mapped to it. Set Control State back to Automatic to allow mapped alarms to operate the
digital output.
► To configure a digital output
1
On DCTools/web, go to
Digital Outputs
. Expand the
Digital Outputs
table.
2
Select a Digital Output. Refer to the I/O Board (IOBGP-xx) Connector Pin-outs on page 138 for
IO Board output numbers.
Other Digital Outputs will be available if additional I/O boards and/or SiteSure-3G modules are
connected. See details in the dc power system Installation and Operation Guide.
3
Configure the following parameters to suit the application.
To change a setting, double-click and select from drop down list or edit the text.