SC300 Handbook
116
Copyright © 2007-2018 Eaton Corporation. All Rights Reserved.
IPN 997-00012-03 B2 Issue B2 July 2018
4
Enter:
Connection Name: <as required>
Comms Enabled:
True
Protocol:
S3P
Connect Using:
Local Network
S3P Address:
0
(
0 = Broadcast, 1-65279 = individual address
)
Server IP Address: The IP Address of the SC300. Allocated by network
administrator.
Server Port:
15000
Telnet
Cleared
5
Press OK. PowerManagerII will now connect to the device connected to the SC300's RS-232
port.
Communications Security
SC300 settings cannot be changed if:
•
All communications are disabled (see SMNP Communications on page 107, and
HTTP/HTTPS Access on page 117), and
•
Keypad access (see details on page 13) is
Read Only
, or PIN Protected and the
keypad access PIN is lost.
In this situation the SC300 will continue to function, but no configuration changes can
be made. Contact your Eaton dc product supplier or Eaton for advice (see Worldwide
Support on page
Serial Communications (USB / RS-232 / Ethernet) Security
S3P Access
S3P is the serial communications protocol used by the SC300 to communicate with
PowerManagerII
via the USB, RS-232 or Ethernet port.
S3P Protocol is not used by the web server.
► To Enable/Disable S3P access
•
On the SC300 keypad go to
Settings
>
Setup
>
S3P
. Select
Enabled
or
Disabled
.
Or:
1
Connect to the SC300 (see details on page 104).
•
Web: go to
System > Interfaces > Remote Access Protocols
>
S3P
.
•
DCTools: go to
Configuration
>
Communications > Remote Access Protocols
>
S3P
.
2
Set
Access
to
Enabled
or
Disabled.