Communications
Copyright © 2007-2018 Eaton Corporation. All Rights Reserved.
IPN 997-00012-03 B2 Issue B2 July 2018
117
Write Access Password
The Write Access Password prevents unauthorized changes to the SC300 configuration (using
PowerManagerII
).
When a Write Access Password is set serial communications access to the SC300 (using
PowerManagerII) is read only. The password must be entered before any setting can be changed.
If a Write Access Password is lost, clear it from the SC300 keypad and change it via the Web.
► To set a Write Access Password
1
Connect to the SC300 with Web (see details on page 104).
•
Web: go to
System > Interfaces > Remote Access Protocols
>
S3P
.
•
DCTools: go to
Configuration
>
Communications > Remote Access Protocols
>
S3P
.
2
Type a password into the
Write Access Password
field.
Passwords are case sensitive, maximum 32 characters.
3
Click the
Apply Changes
button.
► To clear or change a Write Access Password
1
Connect to the SC300 :
•
Web: go to
System > Interfaces > Remote Access Protocols
>
S3P
.
•
DCTools: go to
Configuration
>
Communications > Remote Access Protocols
>
S3P
.
2
Type a new password into the
Write Access Password
field or leave the field blank for no
password control.
3
Click the
Apply Changes
button.
► To clear a Write Access Password from the SC300
1
Use SC300 keypad to go to
Settings
>
Setup
>
Clear Write Access Password
2
Press
Enter
.
The password is now permanently cleared. If required, reset the password with Web.
Web Access Security
Server Access
Access to the SC300 web server can be disabled or set for secure access using Secure Sockets
Layer (SSL) protocol.
SSL is a protocol for transmitting encrypted data over the Internet. URLs that require an SSL
connection start with https: instead of http:. If the network is insecure, Eaton recommends that
you disable HTTP Access.