2 Installation
2.1 Setting the gateway's field bus address
SmartWire-DT Gateway EU5C-SWD-DP
01/13 MN120001Z-EN
www.eaton.eu
11
2 Installation
SWD gateways must only be installed and wired up by qualified electricians
or other persons familiar with electrical engineering.
The SWD gateway is installed in the following order:
•
Adjust the field bus adresse at the device.
•
If the SWD gateway is the first or last module on the PROFI-BUS-DP
field bus, activate a bus termination resistor.
•
Mount the device.
•
Connect the power supply.
•
Connect the SmartWire-DT line.
•
Connect the field bus.
2.1 Setting the gateway's field bus address
Before mounting the device, set the field bus address by using the DIP
switches (DIP = Dual Inline Package). The DIP switches are located under a
cover on the right side of the gateway.
,
Follow the example below in order to configure an address on the gateway -
18 (decimal) is used as an example in this case:
18
dec
= 16 +2 = 1· 2
4
+ 1 · 2
1
The address is to be set at the dip switches.
for EU5C-SWD-DP the following applies:
▶
Use DIP switches 2–8 to set the PROFIBUS module
address. For a list of valid addresses, refer to
device field bus addresses”, page 10.
NOTICE
Changes made to the dip switches' settings will take effect only
after the power supply is turned off and back on again.
DIP Switch
1
2
3
4
5
6
7
8
Description
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
OFF
OFF
OFF
ON
OFF
OFF
ON
OFF
Setting the gateway's field bus address
to a value of 18
dec