5 Take XSoft-CoDeSys-2 into operation
5.1 Installing the GSD file in XSoft-CoDeSys-2
SmartWire-DT Gateway EU5C-SWD-DP
01/13 MN120001Z-EN
www.eaton.eu
31
5 Take XSoft-CoDeSys-2 into operation
The connection of a SWD line via the SWD gateway EU5C-SWD-DP to the
controller XC200 is described in this chapter.
Please check beforehand whether you have a current XSoft-CoDeSys-2 ver-
sion installed with the necessary GSD files.
Please note the list of abbreviations, as the XSoft-CoDeSys-2 PLC program-
ming environment uses different designations from those used in this man-
ual in certain cases
5.1 Installing the GSD file in XSoft-CoDeSys-2
We recommend working with the project-specific GSD file, as it already
includes the assignments between the modular EU5C-SWD-DP field bus
module and the SWD modules on the SWD line in order to make your work
easier.
Likewise you can use the standard GSD file
▶
Copy the standard GSD file or the project-specific GSD file to the folder
intended for storing the standard GSD file.
In the case of the XSoft-CoDeSys-2 Eaton programming system, this
folder will be found on your computer under:
C:\Program Files\Common Files\CAA-Targets\<Version>\PLCConf
where <Version> is the installed configurator version e.g.,
"Moeller V2.3.9."
After doing this, you will be able to use the project-specific GSD file just
as you would the standard GSD file.
▶
Start the XSoft-CoDeSys-2.
▶
Install the GSD files in XSoft-CoDeSys-2 with the
"Tools" -> "Select configuration file" menu option.