background image

3

Instruction Booklet 

IB158002EN

Effective October 2018

Eaton SPD Max Series 

Surge Protective Device 

  

EATON

 www.eaton.com

1.5  Equipment Testing

m

 WARNING

CONDUCTING DIELECTRIC, MEGGER, OR HI-POTENTIAL TESTING WITH THE 

SPD INSTALLED WILL CAUSE INTERNAL DAMAGE TO THE SPD.  THE SPD 

WILL ALSO CAUSE THE TEST TO FAIL.

Every Eaton SPD Max Series unit is tested at the factory for dielec-

tric breakdown.  No further SPD testing is required for installation.
If you desire to test distribution equipment by performing dielectric, 

megger, or hi-potential tests, any installed SPD must be discon-

nected from the power distribution system to prevent damage to the 

unit.
Follow this procedure to safely disconnect the SPD:

1.  For SPDs connected to a circuit breaker or fuse:

a. 3-wire Delta SPDs: Turn off the circuit breaker or remove the 

fuses from the fuse holder to isolate the SPD.

b. Wye and Split phase SPDs: Turn off the circuit breaker or 

remove the fuses from the fuse holder to isolate the SPD and 

remove the Neutral connection on Wye SPDs.

2.0  Installation

m

 WARNING

INSTALLING AN SPD THAT IS IMPROPERLY RATED FOR THE ELECTRICAL 

SYSTEM VOLTAGE COULD CREATE A POTENTIALLY HAZARDOUS 

CONDITION, RESULTING IN INJURY OR EQUIPMENT DAMAGE.

2.1  Preparation for Installation

m

 CAUTION

EATON SPD SERIES PRODUCTS MUST BE INSTALLED OR  REPLACED BY  A 

QUALIFIED ELECTRICIAN TO AVOID INJURY OR EQUIPMENT DAMAGE.

Before installing an Eaton SPD Max Series unit, do the following:

• 

Verify that the area is clear of any dirt, debris or clutter that may 

hamper the installation process.

• 

Verify that there is enough space to install the SPD. See Figure 17 

for dimensions.

• 

Confirm that all tools and equipment needed for the installation 

are available.

• 

Confirm that the system voltage and wiring configuration is the 

same as the SPD you are installing. Check the voltage rating label 

on the side of the SPD.

m

 WARNING

TURN OFF THE POWER SUPPLY BEFORE WORKING IN ANY ELECTRICAL 

CABINET OR ON ANY CIRCUIT BREAKER PANEL.  FAILURE TO DO SO 

COULD RESULT IN INJURY OR DEATH FROM ELECTRICAL SHOCK

NOTICE

A POOR GROUND, OR GROUNDING/BONDING VIOLATIONS, COULD 

PREVENT THE SPD FROM PERFORMING AS SPECIFIED. 

DO NOT USE  THE SPD TO CARRY OR PASS THROUGH GROUND TO OTHER 

DEVICES OR LEADS. DAMAGE TO THE EQUIPMENT MAY RESULT.

• 

Check the facility grounding system. All grounding, bonding, and 

earthing must meet the NEC, CEC and any other national, state 

and local electrical codes.

• 

An insulated grounding conductor that is identical in size and 

insulation material and thickness to the grounded and ungrounded 

circuit supply conductors, except that it is green with or without 

one or more yellow stripes, is to be installed as part of the circuit 

that supplies the SPD Max Series unit.

• 

Refer to Table 250-122 of the NEC to select the appropriate size 

of the grounding conductor.  This grounding conductor is to be 

grounded to earth at the service equipment or other acceptable 

building earth ground such as the building frame in the case of a 

high steel-frame structure.

• 

Any attachment-plug receptacles in the vicinity of the SPD Max 

Series unit are to be of a grounding type, and the grounding con-

ductors serving these receptacles are to be connected to earth 

ground at the service equipment or other acceptable building 

earth ground such as the building frame in the case of a high-rise 

steel-frame structure.

• 

Pressure terminal or pressure slicing connectors and soldering 

lugs used in the installation of the SPD Max Series unit shall be 

identified as being suitable for the material of the conductors.  

Conductors of dissimilar metals shall not be intermixed in a termi-

nal or splicing connector where physical contact occurs between 

dissimilar conductors unless the device is identified for the pur-

pose and conditions of use.

2.2 Installation Locations

Eaton’s SPD Max Series can be installed next to, above, or below 

any existing electrical enclosure.
The ideal mounting location for the Eaton SPD Max Series is as 

close as possible to the electrical enclosure and should be mounted 

in such a way as to minimize the cable length and eliminate any 

sharp bends in the wiring conduit.

Summary of Contents for SPD Series

Page 1: ...Installation 3 3 0 Operating Features 6 4 0 Troubleshooting 8 5 0 Specifications 9 6 0 Ordering Guidelines 10 7 0 Warranty 16 Effective October 2018 Supersedes October 2014 Instruction Booklet IB15800...

Page 2: ...d for UL96A and NFPA 780 Compliance 1 3 Safety Precautions A licensed qualified electrician must complete all instructions in this manual in accordance with the National Electric Code NEC Canadian Ele...

Page 3: ...T BREAKER PANEL FAILURE TO DO SO COULD RESULT IN INJURY OR DEATH FROM ELECTRICAL SHOCK NOTICE A POOR GROUND OR GROUNDING BONDING VIOLATIONS COULD PREVENT THE SPD FROM PERFORMING AS SPECIFIED DO NOT US...

Page 4: ...he SPD enclosure If using the Form C contacts route Form C wires through a separate maximum inch trade size hub and conduit 4 Determine the hole location on the receiving electrical enclosure and eith...

Page 5: ...two SPDs SPD1 and SPD2 the display cable and two SPD Status ribbon cables must be unplugged In either case this is done by loosening the two Cable Hold Down Bracket screws 1 2 turn and sliding the br...

Page 6: ...he Ground terminal block 180o and mount the two terminal blocks in the mounting holes located on the bottom left of the unit See Figure 5 Figure 5 Neutral and Ground Terminal Block re located for Top...

Page 7: ...off power to the unit 2 Remove the two phillips head screws that hold the display 3 Rotate the display to the desired position Be careful not to over stress the display ribbon cable 4 Place the displ...

Page 8: ...lay Neu Gnd Green LED is OFF Neu Gnd Red LED is ON Audible Alarm is ON for models with Neutral connections Neu Gnd protection is compromised or lost Replace SPD See Note Significant surge event Replac...

Page 9: ...ase Wye L N L G N G L L Three phase high leg delta L N L G N G L L Maximum continuous operating voltage MCOV 230V Single Phase 320V L N 320V L G 320V N G 127V 220V WYE 120V 240V Single Split Phase 150...

Page 10: ...10kHz to 100Mhz Surge Counter with Alarm Silence Reset Button 240S 120 240 Split Phase 208Y 120 208 Wye 4W G 220Y 127 220 Wye 4W G 400Y 230 400 Wye 4W G 480Y 277 480 Wye 4W G 600Y 347 600 Wye 4W G 240...

Page 11: ...02EN Effective October 2018 Eaton SPD Max Series Surge Protective Device EATON www eaton com Figure 8 DELTA 3W G with Circuit Breaker Figure 9 Wye 4W G with Circuit Breaker SPD2 only installed in mode...

Page 12: ...r 2018 Eaton SPD Max Series Surge Protective Device EATON www eaton com Figure 10 High Leg Delta 4W G with Circuit Breaker Figure 11 Split Phase 3W G with Circuit Breaker RED RED RED RED RED RED SPD2...

Page 13: ...02EN Effective October 2018 Eaton SPD Max Series Surge Protective Device EATON www eaton com Figure 12 DELTA 3W G with Terminal Block Figure 13 Wye 4W G with Terminal Block SPD2 only installed in mode...

Page 14: ...er 2018 Eaton SPD Max Series Surge Protective Device EATON www eaton com Figure 14 High Leg Delta 4W G with Terminal Block Figure 15 Split Phase 3W G with Terminal Block RED RED RED RED RED RED SPD2 o...

Page 15: ...15 Instruction Booklet IB158002EN Effective October 2018 Eaton SPD Max Series Surge Protective Device EATON www eaton com Figure 16 Product Dimensions...

Page 16: ...ng the SPD or for warranty information call 1 800 809 2772 Option 4 sub option 2 Repair or replacement units will be returned collect If Eaton finds the return to be a manufacturer s defect the produc...

Reviews: