Eaton SPD Series for Mounting External

to Electrical Distribution Equipment

Instruction Manual 

IM01005031E - Rev. 4

Condition

Probable Cause

Solution

Green LEDs ON (1 per phase) and one Green LED ON for 

Neu/Gnd Protection 

Normal operation 

N/A.

Audible Alarm OFF, Form C (N.C.) contact in the CLOSED 

state    

Normal operation

N/A.

Phase Green LED is OFF, same Phase Red LED is ON, 

Audible Alarm is ON     

  

Phase protection compromised or lost 

Extended Temporary Overvoltage (TOV)

Significant surge event

Replace SPD

Check electrical system for TOV sources, correct, replace SPD

Replace SPD

Neu/Gnd Green LED is OFF, Neu/Gnd Red LED is ON, 

Audible Alarm is ON (for models with Neutral connections) 

 

Neu/Gnd protection is compromised or lost 

Significant surge event

Replace SPD 

Replace SPD

All phase Green LEDs OFF, all phase RED LEDs ON, Audible 

Alarm is ON        

All phase protection is compromised or lost 

SPD rated voltage is less than system voltage

Extended Temporary Overvoltage (TOV) 

Significant surge event  

Replace SPD  

Replace SPD with correct voltage model 

Check electrical system for TOV sources, correct, replace SPD

Replace SPD

One of the display Red LEDs is ON. Audible Alarm is OFF         

Audible Alarm Silence button has been 

depressed and Alarm is silenced 

Normal operation

If power is cycled and a fault condition still exists, the Audible 

Alarm will reactivate

All Green and Red LEDs are OFF, LCD display (on Surge 

Counter models) is OFF     

 

SPD is not connected to a power source 

Check system voltage at SPD connection 

Check SPD connections  

4.0 Troubleshooting

Many SPD failures result from improper installation. Once the 

SPD is installed properly, it is a highly reliable unit.
If the SPD does not function properly, first confirm that it is 

installed properly. See Section 2, “

Installation.

” 

If the SPD malfunctions after it has been operating routinely, 

refer to Table 2, 

Troubleshooting Chart

. This Troubleshooting 

Chart identifies possible causes and solutions to the malfunc-

tion.  Further assistance may be obtained by calling Eaton’s 

Applications Engineers, at 1-800-809-2772, option 4, sub-option 

2, including being directed to the warranty process if applicable. 

Table 2.  Troubleshooting Chart

Summary of Contents for SPD120480D3M

Page 1: ...l Distribution Equipment Instruction Manual IM01005031E Effective November 2012 Rev 2 Table of Contents 1 0 Introduction 2 0 Installation 3 0 Operating Features 4 0 Troubleshooting 5 0 Specifications...

Page 2: ...and are intended to be installed in applications with a degree of protection rated IP 20 1 3 Safety Precautions A licensed qualified electrician must complete all instructions in this manual in accord...

Page 3: ...eck the facility grounding system All grounding bonding and earthing must meet the NEC and any other national state and local electrical codes 2 2 Installation Locations Eaton s SPD Series can be inst...

Page 4: ...state and local electrical codes when mak ing these connections Figure 2 NEMA 1 With Flushmount Suffix L 4 IM01005031E Rev 2 Effective November 2012 Eaton SPD Series For Mounting External To Electrica...

Page 5: ...K Figure 4 NEMA 4 4X Suffix N P 5 IM01005031E Rev 2 Effective November 2012 Eaton SPD Series For Mounting ExternalTo Electrical Distribution Equipment eaton corporation www eaton com NEMA 1 Suffix K...

Page 6: ...v 2 Effective November 2012 Eaton SPD Series For Mounting External To Electrical Distribution Equipment eaton corporation www eaton com NEMA 1 With Disconnect Suffix M Figure 5 NEMA 4 4X With Disconne...

Page 7: ...ting External to Electrical Distribution Equipment BLUE WHITE RED WHITE ORANGE WHITE COMMON NORMALLY OPEN NORMALLY CLOSED Figure 7 Sidemount Form C Wires Figure 8 Split Phase Units Figure 9 3 Phase De...

Page 8: ...nt for each feature package Each display has both green and red light emitting diodes LEDs to indicate the status of the protection on each phase Green indicates the phase is fully protected Red indic...

Page 9: ...the display 3 Remove the two phillips head screws that hold the display 4 Rotate the display to the desired position Be careful not to overstress the display ribbon cable 5 Place the display back onto...

Page 10: ...Significant surge event Replace SPD Replace SPD with correct voltage model Check electrical system for TOV sources correct replace SPD Replace SPD One of the display Red LEDs is ON Audible Alarm is O...

Page 11: ...nits 208Y 220Y 230L 240S 240D and 240H voltage codes 0 6W 400Y 480Y and 480D Basic voltage codes 1 7W 600Y and 600D voltage codes 2 1W Protection modes Single split phase L N L G N G L L Single phase...

Page 12: ...colored LED to indicate Protection Status of the N G Mode on units with a Neutral Wire Audible alarm with Silence button Form C Relay Contact EMI RFI filtering Providing up to 50dB of Noise Attenuatio...

Page 13: ...m determined by Eaton to be defec tive The giving of or failure to give any advice or recommenda tions by Eaton shall not constitute any warranty by or impose any liability upon Eaton The foregoing co...

Page 14: ...nd conditions outlined in appropriate Eaton selling policies or other contractual agreement between Eaton and the purchaser THERE ARE NO UNDERSTANDINGS AGREEMENTS WARRANTIES EXPRESSED OR IMPLIED INCLU...

Reviews: