Specifications are subject to change without notice. Copyright 2015 Eaton Industries, Mascot. NSW.
Technical Specification SPD150i
Doc# 5100SPD150i Rev1
Page 1 of 2
T
ECHNICAL
S
PECIFICATION AND
INSTALLATION GUIDE
SPD150i SURGE
DIVERTER
( IEC61643-11 Class I & II, 150kA, 2 mode, 220-
300vac, L-E or L-N )
APPLICATIONS
Primary power circuits
Telecommunication Systems / Rectifiers
Process and Control Systems
Computer Systems / Medical Systems
FEATURES
Patented MTMOV technology
( Failsafe thermal disconnect )
UL1449 ed3 Type 4 listed components
150kA, 2 mode, L-N or L-E
UL94-V0 ABS din rail mount housing
Din 43880 form factor 4 din wide
Dry contact alarm
LED visual indicators for protection,
power and fault conditions.
FUNCTIONAL DESCRIPTION
The SPD150i is designed to protect single and three
phase power systems against damage from surges
and spikes caused by lightning and other electrical
sources. The unit is intended for point of entry or
main board protection and is connected in parallel
with the power system via HRC fuses.
This model ( SPD150i ) is designed for use in
systems with a grounded neutral in L-N mode. If
your system does not have a grounded Neutral or
is of a different voltage, this model is NOT
suitable.
OPERATION
Indicators - The operation status of the SPD150i is
indicated by leds on the front panel. The ‘OK’ ( blue )
light indicates that power is applied to the SPD150i
The ‘FAULT’ light ( red ) indicates that the surge
protection circuitry is damaged and the unit should be
replaced. The additional 3 leds ( blue ) indicate the
status of each MOV element. When the fault indicator
lights, the protection relay contacts change over. The
power failure alarm will operate when mains voltage
falls below 180VAC.
PHYSICAL AND ELECTRICAL SPECIFICATIONS
Model
SPD150i
Number of ports
1 Port
Method of mounting
Fixed. DIN Rail mount
Input voltage – Uc
220-300vac 1P, 380-
480vac 3P
Maximum continuous voltage –
MCOV
320 L-N, L-E
Temporary overvoltage - TOV
350VAC L-N, 15 mins
Service type
TT, TN, TN C-S or any 1 or
3phase system with a
grounded neutral.
Test classification (IEC61643-11)
Class II
Maximum over current protection
125A
Protection modes
Line-Neutral, Line-Earth
Inom 8/20us (Line-Neutral/Earth).
Nominal surge life.
60kA
Imax 8/20us (Line-Neutral/Earth).
Maximum surge level.
120kA
Residual voltage (Vpl) (Line-
Neutral/Earth). (Let through
voltage)
<1000v (3kA, 8/20us,
( IEC61643-11)
Safety disconnect
Series thermal fusing on
MOV’s
External disconnector
requirement
Max 125A HRC fuse
Terminations
Power 16mm
2
Alarms/indicators
5 LED display, dry
contact alarm relay
output – 250VAC/32VDC,
5A, 5kV isolation
Enclosure rating
IP20
Standards. Designed in
accordance with :
IEC61643-11, ANSI/IEEE
C62.41 Cat A & B,
AS1768-2007 Cat A & B,
UL1449ed3 type 4
Installation instructions
Supplied with unit.
Dimensions
70W x 58D x 90H (mm)
Weight
200g
Environment
-10 to 60
C, 0 to 95%RH
(non-condensing)
Warranty
5 years, workmanship
and materials