background image

INS #

Brand Logo  
reversed out of 
black

INS #

IB505051EN   049-304

Installation Instructions for the Sure-Lites LPX Combination Exit/Emergency Lights 

and Exits with Self Diagnostics

 WARNING 

Risk of Fire/Electric Shock

If not qualified, consult an electrician.

  WARNING 

Risk of Electric Shock

Disconnect power at fuse or circuit breaker before 

installing or servicing.

Important Safeguards

WHEN USING ELECTRICAL EQUIPMENT, BASIC SAFETY 
PRECAUTIONS SHOULD ALWAYS BE OBSERVED INCLUDING 
THE FOLLOWING.

1  READ AND FOLLOW ALL SAFETY INSTRUCTIONS 

2  Do not use outdoors. 

3  Do not use in hazardous locations, or near gas or electric 

heaters. 

4  Do not let power supply cords touch hot surfaces. 

5  Do not use this equipment for other than the intended use. 

6  Installation is to be performed only by qualified personnel. 

7  Install in accordance with National Electric Code and local 

regulatory agency requirements. 

8 The use of accessory equipment not recommended by the 

manufacturer may cause an unsafe condition. 

9  Equipment should be mounted in locations and at heights 

where it will not readily be subjected to tampering by 
unauthorized personnel. 

10  SAVE THESE INSTRUCTIONS

MAX MOUNTING HEIGHT:

17.24 FT

WALL MOUNT INSTALLATION

1  Extend unswitched 24 hour AC supply of rated voltage to 

junction box (by others). Leave at least 18 inches of slack. 
Circuit should not be energized at this time.

2  Remove the stencil face and lens assembly by applying a 

screwdriver to the snaps located at the top and bottom of 
the stencil face.

3  Knock out the appropriate mounting pattern and wire pass 

hole to match junction box. Use the integrated wire hook 
in the backplate to hold the wires in place so that there is 
no shadowing on the face of the sign (see Figure 1). 

4  Connect power supply and ground in accordance with 

local codes. Wire connections as follows: 277VAC/240VAC 
line to Orange lead or 120V line to Black lead; Neutral or 
240V (Common) to white lead (see Schematic). Cap unused 
line lead.  

Note:

 Connections must be the enclosure rated area of the 

frame (top left corner) or junction box (see Figure 1).

5  Mount to junction box.
6  Determine which color sign face is needed. If red is 

needed, proceed to step 9

7  If green is the desired color, remove the red lens from 

the stencil and replace it with the green lens provided. 
(Installation is the reverse of removal.).

8  On the LED circuit board, locate the red/green jumper (See 

Schematic).The jumper should be in the red position per 
the silk screen printing on the board. Pull gently upward 
on the jumper, then shift it one pin over to activate the 
green LEDS.

9  If the unit has remote capacity, LED remotes can be 

connected using the violet (+) and yellow (-) wires. (See 
Schematic).

10 Energize AC supply, LED display will come on.
11 Replace the stencil cover assembly.
12 Remove EZ Key to connect battery.  Battery will not charge 

with EZ key in place.  Allow 24 hours for charging with 120 
or 277V input, 48 hours with 240V input.

Reviews: