USAGE INSTRUCTIONS FOR THE SURE-LITES EAGLE EYE
SELF DIAGNOSTICS
The Sure-Lites Eagle Eye Self Diagnostics is continuously
monitoring your emergency fixture, and will signal any failure
through the 3 color indicator LED.
Initial Operation
When the unit is first powered up, it will go into a 24 hour fast
charge, indicated by the indicator LED pulsing green. Once the
unit has fully charged, it will perform a self-calibration, after
which the LED will change to steady green, indicating the unit
is fully charged and float charging the battery to maintain
readiness.
Automatic Testing
The unit will perform a battery capacity, lamp/LED, and charge
circuit test every 30 days for 30 seconds. During this time, the
indicator LED will change to a steady yellow. It will perform a
full battery capacity (90 minute) test once per year. During this
time, the indicator LED will change to a blinking yellow.
Manual Testing
• 10 Second “Installation” test – Press and release the test
button once during fast charge (blinking green) to initiate
a 10 second quick test. The sign and LED lamps will switch
to emergency mode for 10 seconds allowing the installer to
verify proper installation of the unit, and the LED indicator
will turn solid yellow.
• 30 Second Test - Press and release the test button once
during float charge (steady green). The indicator LED will
turn steady yellow to indicate the unit is performing a 30
second test of the batteries and LED lamps.
• 90 Minute Test - Press and release the test button a second
time during a 30 second test (steady yellow) to change to
a 90 minute test. During this test, the LED indicator will
change to blinking yellow, and the circuit will perform a full
battery capacity, charge circuit, and LED test.
• Canceling Test – Press and release the test button during the
90 minute test (flashing yellow) to return the fixture to its
original state (fast charge or float charge).
Clearing Failure Codes
• A battery failure (LED two blink red) can be cleared by
replacing the battery. Disconnecting the battery and AC
power, or performing a full 90 minute discharge, will reset
the error code, however, it will return if the battery is faulty.
• Charge Circuit (LED three blink red) and lamp/LED failure
(LED four blink red) will clear when the unit successfully
passes a manual or automatic 30 second test.
Indicators
• LED Off - No power to unit, emergency mode.
• LED Steady Green - Unit is fully charged and is float
charging the battery to maintain readiness.
• LED Green Pulse - Unit is in a 24 hour fast charge of the
battery.
• LED Two Blink Red - Battery has failed a capacity test, or
the battery is disconnected. See “Clearing Failure Codes”
above.
• LED Three Blink Red - Battery charge circuit has failed. See
“Clearing Failure Codes” above.
• LED Four Blink Red - Lamps have burned out, or 50% or
more of the sign LEDs have failed. See “Clearing Failure
Codes” above.
• LED Steady Yellow - 30 second test or 10 second quick test
(Fast Charge only).
• LED Blinking Yellow - 90 minute test.
SURE-LITES
STEADY BLINK
GREEN - FAST
CHARGE
STEADY YELLOW -
QUICK TEST
4 BLINK RED - LAMP /
LED FAILURE
3 BLINK RED - CHARGE
CIRCUIT FAILURE
STEADY BLINK YELLOW
- 90 MINUTE TEST
STEADY GREEN -
FULL / FLOAT
CHARGE
2 BLINK RED -
BATTERY FAILURE
OFF - EMERGENCY
MODE / POWER OFF
Eagle Eye
Self-Diagnostics
Installation Instructions for LPX Combination Exit/Emergency Lights and Exits with Self