INS #
IB505063EN 049-306
SURE-LITES
Installation Instructions for the Sure-Lites Lites SELA Architectural Emergency Light
with Self Diagnostics
WARNING
Risk of Fire/Electric Shock
If not qualified, consult an electrician.
WARNING
Risk of Electric Shock
Disconnect power at fuse or circuit breaker before
installing or servicing.
Important Safeguards
WHEN USING ELECTRICAL EQUIPMENT, BASIC SAFETY
PRECAUTIONS SHOULD ALWAYS BE OBSERVED INCLUDING
THE FOLLOWING.
1. READ AND FOLLOW ALL SAFETY INSTRUCTIONS
2. Do not use outdoors.
3. Do not use in hazardous locations, or near gas or electric
heaters.
4. Do not let power supply cords touch hot surfaces.
5. Use caution when servicing batteries. Battery acid can
cause burns to skin and eyes. If acid is spilled on skin or in
eyes, flush acid with fresh water and contact a physician
immediately.
6. Do not use this equipment for other than the intended use.
7. Installation is to be performed only by qualified personnel.
8. Install in accordance with National Electric Code and local
regulatory agency requirements.
9. The use of accessory equipment not recommended by the
manufacturer may cause an unsafe condition.
10. Equipment should be mounted in locations and at heights
where it will not readily be subjected to tampering by
unauthorized personnel.
11. SAVE THESE INSTRUCTIONS
MAX MOUNTING HEIGHT: 17 ft.
INSTALLATION
1. De-energize the circuit to which the fixture will be
connected.
2. Remove fixture assembly from back box provided. (See
Fig. 1).
3. Plan how wiring will be extended to the fixture. Knock
out the appropriate conduit KO and extend wiring to the
fixture.
4. If bar hanger installation is desired, proceed to step 6.
5. If installation without bar hangers is desired, remove the
bar hangers by removing the four 6-32 screws holding
the bar hanger brackets in place. The back box can now
be screwed or nailed directly to a stud or other suitable
surface. Proceed to step 8.
6. Bar hangers for this fixture are of interlocking design to
allow positioning of housing along entire length of bars.
Position bar hangers to the desired position between the
studs. Bar hangers may be shortened to fit 12” framing by
breaking at score lines (Hanger bar range is 8-24”). Pass
bar hangers through each end until the bars overlap, then
break off at score lines (no tools required and bar hangers
do not need to be removed from bracket). (See Fig. 2)
Secure hanger bars with nails or screws into studs.
7. Adjust position of back box on bar hangers as needed. To
secure back box in positon, crimp tabs on bracket over bar
hangers.
8. Retrieve fixture assembly.
9. Connect power supply and ground in accordance with
local codes. Connect the incoming wires to the fixture’s
power supply wires using the wire nuts provided. Connect
the white wire to neutral. Connect 277VAC line to Orange
lead or 120V line to Black lead, cap the unused lead. (See
Schematic).
10. Place the fixture assembly and wiring in the back box, and
secure to the fixture using long 6-32 screws. (See Fig. 1).
11. Remove the EZ Key. Lamps will light. Adjust the heads as
needed.
12.Energize AC supply. The test button should illuminate and
LED heads will illuminate briefly when the test button is
pushed or laser test is engaged.
13.Replace the EZ Key if the fixture will be de-energized for a
prolonged period of time.
14. Snap on the decorative cover, if desired (See Fig. 3).
Decorative cover is sold separately.
FLEXIBLE CONDUIT ONLY
X