Installation Instructions for the Sure-Lites SELA Architectural Emergency Light with Self Diagnostics
ACTIVATING TIME DELAY
The SELA series has an integrated time delay circuit that
allows them to remain in emergency mode 15 minutes after
power is restored. To activate the time delay, open the fixture
by unsnapping the fixture assembly cover from the fixture
assembly body (see Fig. 4) and then remove the jumper on the
circuit board labeled TDI/J1 (see Figure 5).
OPERATION
The Sure-Lites Self Diagnostics circuitry is continuously
monitoring your emergency fixture, and will signal any failure
through the 3 color indicator LED.
Initial Operation
When the unit is first powered up, it will go into a 24 hour fast
charge, indicated by the indicator LED pulsing green. Once the
unit has fully charged, it will perform a self-calibration, after
which the LED will change to steady green, indicating the unit
is fully charged and float charging the battery to maintain
readiness.
Automatic Testing
The unit will perform a battery capacity, lamp/LED, and charge
circuit test every 30 days for 30 seconds. During this time, the
indicator LED will change to a steady yellow. It will perform a
full battery capacity (90 minute) test once per year. During this
time, the indicator LED will change to a blinking yellow.
Manual Testing
• 10 Second “Installation” test – Press and release the test
button once during fast charge (blinking green) to initiate a 10
second quick test. The sign will switch to emergency mode for
10 seconds allowing the installer to verify proper installation of
the unit, and the LED indicator will turn solid yellow.
• 30 Second Test -Press and release the test button once during
float charge (steady green). The indicator LED will turn steady
yellow to indicate the unit is performing a 30 second test of the
batteries and lamps/LEDs.
• 90 Minute Test -Press and release the test button a second
time during a 30 second test (steady yellow) to change to a 90
minute test. During this test, the LED indicator will change to
blinking yellow, and the circuit will perform a full battery
capacity, charge circuit, and LED test.
• Canceling Test – Press and release the test button during the
90 minute test (flashing yellow) to return the fixture to its
original state (fast charge or float charge).
Laser Testing
The SELA is equipped with a Laser Test function, that allows the
unit to be manually tested without the need to physically press
the test button. Shining a laser pointer in the hole marked
“LASER TEST” on the bottom of the unit has the same effect as
a press and release of the test button.
Figure 4
Battery
Compartment
Cover
Figure 2
Bend Outwards
At Score Line
Score Lines
Figure 3
Snap On Decorative Cover (Sold Separately)
Snap Locations
Cross
Section
View
Fixture Assembly Cover
Fixture Assembly body
Battery
Figure 1
Wall Stud
Bar Hangers
Black Box
Fixture Assembly
EZ Key
2.125
"
#6-32 Screws