Installation Instructions for the Sure-Lites SELA Architectural Emergency Light with Self Diagnostics
© 2017 Eaton
All Rights Reserved
Printed in USA
Impreso en los EE. UU.
Publication No. IB505063EN
Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com
Eaton is a registered trademark.
All trademarks are property
of their respective owners.
Eaton es una marca comercial
registrada. Todas las marcas
comerciales son propiedad de sus
respectivos propietarios.
Warranties and Limitation of Liability
Please refer to
www.eaton.com/LightingWarrantyTerms
for our terms and conditions.
SCHEMATIC
ORANGE LEAD - TO 277VAC
BLACK LEAD - TO 120VAC
BATTERY
CHARGER/
DRIVER
PCB
TIME DELAY
JUMPER
LOCATION
WHITE LEAD - TO NEUTRAL
LED
HEADS
Clearing Failure Code
• A battery failure (LED two blink red) can be cleared by
replacing the battery. Disconnecting the battery and AC power
or performing a full 90 minute discharge will also reset the
error code. However, the error code will return if the battery is
faulty.
• Charge Circuit (LED three blink red) and lamp/LED failure
(LED four blink red) will clear when the unit successfully passes
a manual or automatic 30 second test.
Indicators
• LED Off - No power to unit or in emergency mode.
• LED Steady Green - Unit is fully charged and is float charging
the battery to maintain readiness.
• LED Green Pulse - Unit is in a 24 hour fast charge of
the battery.
• LED Two Blink Red - Battery has failed a capacity test or the
battery is disconnected. See “Clearing Failure Codes” above.
• LED Three Blink Red - Battery charge circuit has failed. See
“Clearing Failure Codes” above.
• LED Four Blink Red - Lamps have burned out, or on an EXIT/
Combo, 50% or more of the LEDs have failed. See “Clearing
Failure Codes” above.
• LED Steady Yellow - 30 second test or 10 second quick test
(Fast Charge only).
• LED Blinking Yellow - 90 minute test.
MAINTENANCE
None required. Replace the batteries as needed according
to ambient conditions. However, we recommend that the
equipment be tested regularly in accordance with local codes.
NOTE:
Servicing of any parts should be performed by qualified
personnel. Only use replacement parts supplied by Eaton
Lighting.
CAUTION:
This equipment is furnished with a sophisticated low
voltage battery dropout circuit to protect the battery from over
discharge after its useful output has been used. Allow 24 hours
recharge time after installation or power failure for 90 minute
testing.
TROUBLE SHOOTING GUIDE
If LED heads or charge indicator LED does not illuminate, check
the following:
1. Check AC supply – verify that unit has 24 hour AC supply.
2. Unit is shorted or battery is not connected.
3. Battery discharged. Permit unit to charge for 24 hours and
then re-test.
4. If following the above trouble shooting hints does not
solve your problem, contact your local Eaton Lighting
representative for assistance.
Figure 5
Time Delay Jumper Pin Location