Page 10 (60)
Motor Pump Enhanced Protection Application
SV9000
Group 3, Output and supervision parameters
Cod
e
Parameter
Range
Step
Default
Custom
Description
Page
3.1
Analog output function
0—11
1
1
0 = Not used
Scale 100%
1 = O/P frequency (0—f
max
)
2 = Motor speed (0—max. speed)
3 = O/P current
(0—2.0 x I
nSV9
)
4 = Motor torque (0—2 x T
nSV9
)
5 = Motor power (0—2 x P
nSV9
)
6 = Motor voltage (0—100% x U
nM
)
7 = DC-link volt.
(0—1000 V)
8 = Input signal V
in
9 = Input signal I
in
10 =Reference frequency
11 =Reference torque
24
3.2
Analog outp. filter time
0.01—10 s
0.01
1.00
24
3.3
Analog outp. inversion
0—1
1
0
0 = Not inverted
1 = Inverted
24
3.4
Analog output minimum
0—1
1
0
0 = 0 mA
1 = 4 mA
25
3.5
Analog output scale
10—1000%
1%
100%
25
3.6
Output freq. limit 1
supervision function
0—2
1
0
0 = No
1 = Low limit
2 = High limit
25
3.7
Output freq. limit 1
supervision value
0—f
max
(par. 1
.
2)
0.1
Hz
0 Hz
25
3.8
Output freq. limit 2
supervision function
0—2
1
0
0 = No
1 = Low limit
2 = High limit
25
3.9
Output freq. limit 2
supervision value
0—f
max
(par.1
.
2)
0.1
Hz
0 Hz
25
3.10
Torque limit supervision
function
0—2
1
0
0 = No
1 = Low limit
2 = High limit
26
3.11
Torque limit supervision
value
0—200%
xT
nSV9
1%
100%
26
3.12
Reference limit
supervision function
0—2
1
0
0 = No
1 = Low limit
2 = High limit
26
3.13
Reference limit
supervision value
0—f
max
(par. 1. 2)
0.1
Hz
0 Hz
26
3.14
Extern. brake Off-delay
0—100.0 s
0.1 s
0.5 s
26
3.15
Extern. brake On-delay
0—100.0 s
0.1 s
1.5 s
26
3.16
Frequency converter
temperature limit
supervision function
0—2
1
0
0 = No
1 = Low limit
2 = High limit
27
3.17
Frequency converter
temperature limit value
-10—+75°C
1°C
+40°C
27
3.18
I/O-expander board (opt.)
analog output content
0—9
1
3
See parameter 3. 1
27
3.19
I/O-expander board (opt.)
analog output filter time
0.01—10 s
0.01
1.00
See parameter 3. 2
27
3.20
I/O-expander board (opt.)
analog output inversion
0—1
1
0
See parameter 3. 3
27
3.21
I/O-expander board (opt.)
analog output minimum
0—1
1
0
See parameter 3. 4
27
3.22
I/O-expander board (opt.)
analog output scale
10—1000%
1
100%
See parameter 3. 5
27
3.23
Analog output offset
(basic control board)
-100% —
100.0%
1
100%
27
3.24
I/O-expander board (opt.)
analog output offset
-100% —
+100.0%
1
100%
27